16 Maintenance Guide
In order to ensure optimal performance of the unit, checks and inspections on the unit and the field wiring must be carried out
regularly. Please request a licensed technician for carry out maintenance job.
Before carried out any maintenance or repair work, and removing the front plate of heat exchanger unit, always switch off all power
supply (i.e. indoor unit power supply, heater power supply and sanitary tank power supply).
Below checks must be carried out at least once a year.
1. Water pressure
Water pressure should not lower than 0.05 MPa (with inspects the pressure gauge). If necessary add tap water into boiler
tank. Refer to boiler tank installation instruction for details on how to add water.
2. Pressure relief valve
• Check for correction operation of pressure relief valve by turn up the lever to become horizontal. (Refer to figure below)
• If you do not hear a clacking sound (due to water drainage), contact your local authorized dealer.
• Turn down the lever after checking finish.
• In case the water keeps drained out from the unit, switch off the system, and then contact your local authorized dealer.
3. Indoor unit control board area
Thorough visual inspection of the control board and look for defects, i.e. loose connection, melting of wire insulator and etc.
4. RCCB
Ensure the RCCB set to “ON” condition before check RCCB.
Turn on the power supply to the indoor unit.
This testing could only be done when power is supplied to the indoor unit.
• Push the “TEST” button on the RCCB. The lever would turn down and indicate “0” and indicate green colour if it functions
normal.
• Contact authorized dealer if the RCCB malfunction.
• Turn off the power supply to the indoor unit.
• If RCCB functions normal, set the lever to “ON” again after testing finish.
5. How to release the trapped air in water circuit
• Turn up the lever to become horizontal. (Refer to figure “Pressure relief valve”). The trapped air will be drained out together
with water. After few seconds, turn down the lever to stop the water drainage.
• Repeat it until the bubbling sound disappear.
Becareful not to touch parts other than RCCB test button when the power is supplied to Indoor Unit. Else, electrical shock may
happen.
Summary of Contents for WH-SDC07C3E5
Page 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 Weekly Timer Setting ...
Page 21: ...21 4 1 3 Setting Up The Special Functions ...
Page 22: ...22 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 23: ...23 5 Dimensions 5 1 Indoor Unit ...
Page 24: ...24 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 25: ...25 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 27: ...27 ...
Page 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 30: ...30 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 31: ...31 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 35: ...35 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...
Page 40: ...40 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 42: ...42 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 66: ...66 Solar Priority is Set Solar Priority is Not Set ...
Page 69: ...69 Heat Tank Heating No Priority Solar Priority Set ...
Page 70: ...70 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 80: ...80 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 81: ...81 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 129: ...129 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 130: ...130 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 155: ...155 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 158: ...158 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 159: ...159 ...
Page 162: ...162 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 163: ...163 ...