47
• Do not insert this hose into sewage hose or cleaning hose
that may generate ammonia gas sulfuric gas etc.
• If necessary, use hose clamp to further tighten the hose at
drain hose connector to prevent it leakage.
• The water may drip from drain hose. Therefore must ensure
the outlet of the hose is always not closed or blocked.
11.3.4.
CONNECT THE CABLE TO THE INDOOR UNIT
1. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4
×
4.0 or 6.0 mm
2
flexible cord, type designation 60245 IEC 57 or heavier cord.
• Ensure the colour of wires of outdoor unit and the terminal Nos. are the same to the indoor unit’s respectively.
• Earth wire shall be longer than the other wires as shown in the figure for the electrical safety in case of the slipping out of the
cord from the Holder (Clamper).
2. Cable connection to the power supply through isolating device (Disconnecting means).
• Isolating device (Disconnecting means) should have minimum 3.0 mm contact gap.
• Connect the approved polychloroprene sheathed power supply 1 cord (3
×
4.0 or 6.0 mm
2
) and power supply 2 cord (3
×
4.0
mm
2
) and type designation 60245 IEC 57 or heavier cord to the terminal board, and to the other end of the cord to isolating
device (Disconnecting means).
3. To avoid cable and cord harmed by sharp edge, cable and cord must go through bushing (located at the bottom of indoor unit)
before carry out electrical connection. The bushing must be used and must not take off.
Connecting with external device (optional)
1.
All connections
shall
follow to the local national wiring standard.
2. It is strongly recommended to use manufacturer-recommended parts and accessories for installation.
3. Maximum output power of booster heater should be
≤
3 kW. Booster Heater’s cord must be (3
×
min 1.5 mm
2
), of type
designation 60245 IEC 57 or heavier.
4. Two-way Valve shall be spring and electronic type, refer to “Field Supply Accessories” table for details. Valve’s cable shall be
(3
×
min 0.5 mm
2
), of type designation 60245 IEC 57 or heavier, or similarly double insulation sheathed cable.
* note: - Two-way Valve shall be CE marking compliance component.
- Maximum load for the valve is 3VA.
5. Three-Way Valve shall be spring and electronic type. Valve’s cable shall be (3
×
min 0.5 mm
2
), of type designation 60245 IEC
57 or heavier, or similarly double insulation sheathed cable.
* note: - Shall be CE marking compliance component.
- It shall be directed to heating mode when it is OFF.
- Maximum load for the valve is 3VA.
6. Receiver shall be connected to “Room Thermostat”, refer to “Field Supply Accessories” table for details. Receiver’s cable
must be (4 or 3
×
min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed cable. (connection refer to
Diagram 5.2).
7. Tank OLP’s cable must be (2
×
min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: if such connection deemed NO necessary for tank OLP, please connect jumper between terminal no #13 and #14.
8. Tank Sensor shall be resistance type, please refer to Graph 5.1 for the characteristic and details of sensor. Its cable shall be
(2 x min 0.3 mm
2
), double insulation layer (with insulation strength of min 30V) of PVC-sheathed or rubber-sheathed cable.
9. External Controller shall be connected to 1-pole switch with min 3.0mm contact gap. (connection refer to Diagram 5.3). Its
cable must be (2
×
min 0.5 mm
2
), double insulation layer of PVC-sheathed or rubber-sheathed cable.
* note: - When making such connection, kindly remove the jumper between terminal no #17 and #18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than 3A
rms
.
10. Solar Three-way Valve’s cable shall be (3
×
min 0.5 mm
2
), double insulation layer PVC-sheathed or rubber-sheathed cable.
11. Must install Solar Connection PCB to indoor unit when Solar Pump Station is utilized. Refer Solar Connection PCB’s
installation instruction for detail of installation.
Summary of Contents for WH-SDC07C3E5
Page 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 Weekly Timer Setting ...
Page 21: ...21 4 1 3 Setting Up The Special Functions ...
Page 22: ...22 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 23: ...23 5 Dimensions 5 1 Indoor Unit ...
Page 24: ...24 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 25: ...25 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 27: ...27 ...
Page 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 30: ...30 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 31: ...31 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 35: ...35 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...
Page 40: ...40 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 42: ...42 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 66: ...66 Solar Priority is Set Solar Priority is Not Set ...
Page 69: ...69 Heat Tank Heating No Priority Solar Priority Set ...
Page 70: ...70 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 80: ...80 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 81: ...81 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 129: ...129 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 130: ...130 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 155: ...155 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 158: ...158 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 159: ...159 ...
Page 162: ...162 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 163: ...163 ...