14.1.6.
Low Frequency Protection Control 1
• When the compressor continuously operates at frequency lower than 25 Hz for 240 minutes, the operation frequency will change
to 24 Hz for 2 minutes.
14.1.7.
Low Frequency Protection Control 2
• When all the below conditions comply, the minimum compressor frequency will change to lower frequency.
14.1.8.
High pressure sensor control
• Purpose:
- To protect the system operation.
• Detection period:
- After compressor on for 5 minutes.
• Detection conditions:
- When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
• After detection:
- When abnormality is detected continue 5 seconds, unit stop operation.
- OFF/ON control panel LED will blink (H64 error occurs).
14.1.9.
Outside Temperature Current Control
14.1.10. Crank case heater control
• Purpose:
- For compressor protection during low outdoor ambient operation (during heating low temperature operation).
• Control content:
a. Trigger heater START conditon
• when the outdoor air temperature is 4
°
C or below, and discharge temperature is 11.6
°
C or below.
b. Resetting heater STOP condition
1. when the outdoor air temperature exceeds entry condition (6
°
C)
2. when the discharge temperature exceeds entry condition (18.8
°
C)
Temperature, T, for:
Heating
Cooling
Outlet water (
°
C)
T < 14 or T 48
T < 14 or T 30
Outdoor air (
°
C)
T < 4 or T 24
T < 13 or T 38
Indoor heat exchanger (
°
C)
T
0
T < 30
Summary of Contents for WH-SDC07C3E5
Page 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 Weekly Timer Setting ...
Page 21: ...21 4 1 3 Setting Up The Special Functions ...
Page 22: ...22 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 23: ...23 5 Dimensions 5 1 Indoor Unit ...
Page 24: ...24 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 25: ...25 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 27: ...27 ...
Page 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 30: ...30 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 31: ...31 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 35: ...35 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...
Page 40: ...40 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 42: ...42 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 66: ...66 Solar Priority is Set Solar Priority is Not Set ...
Page 69: ...69 Heat Tank Heating No Priority Solar Priority Set ...
Page 70: ...70 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 80: ...80 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 81: ...81 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 129: ...129 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 130: ...130 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 155: ...155 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 158: ...158 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 159: ...159 ...
Page 162: ...162 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 163: ...163 ...