12 Installation Instruction
WH-UD12CE5-A WH-UD14CE5-A WH-UD16CE5-A
12.1. Select The Best Location
INDOOR UNIT
• There should not be any heat source or steam near the unit.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 800 mm.
• Must install on a vertical wall.
• When install electrical equipment at wooden building of
metal lath or wire lath, according to electrical facility
technical standard, no electrical contact between equipment
and building is allowed. Insulator must be installed in
between.
• Do not install the unit at outdoor. This is designed for indoor
installation only.
• When connecting solar pump station cable between indoor
unit and solar pump station, the distance between both
apparatuses shall be 2 ~ 8 meters and the length of the said
cable must be shorter than 10 meter.
Failure to do so may lead to abnormal operation to the
system.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• Avoid location where ambient temperature is below -20
°
C.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If outdoor unit installed near sea, region with high content of
sulphur or oily location (e.g. machinary oil, etc), it lifespan
maybe shorten.
•
• If piping length is over 30 m, additional refrigerant should be
added as shown in the table.
Example : For SDC12C6E5/UD12CE5**
If piping length is 40m, the quantity of additional refrigerant
should be 500g. [(40-30)m x 50 g/m = 500g]
12.2. Indoor/Outdoor Unit
Installation Diagram
• When installing the product in a place where it
will be affected by typhoon or strong wind
such as wind blowing between buildings,
including the rooftop of a building and a place
where there is no building in surroundings, fix
the product with an overturn prevention wire,
etc. (Overturn prevention fitting model
number: K-KYZP15C)
Model
Piping size
Rated
Length
(m)
Max
Eleva-
tion
(m)
Min.
Piping
Length
(m)
Max.
Piping
Length
(m)
Addi-
tional
Refrige-
rant
(g/m)
Gas
Liquid
SDC12C6E5/
UD12CE5**
ø15.88
mm
(5/8”)
ø9.52
mm
(3/8”)
5~7.5
30
3
40
50
SDC14C6E5/
UD14CE5**
ø15.88
mm
(5/8”)
ø9.52
mm
(3/8”)
5~7.5
30
3
40
50
SDC16C6E5/
UD16CE5**
ø15.88
mm
(5/8”)
ø9.52
mm
(3/8”)
5~7.5
30
3
40
50
Summary of Contents for WH-SDC07C3E5
Page 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 Weekly Timer Setting ...
Page 21: ...21 4 1 3 Setting Up The Special Functions ...
Page 22: ...22 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 23: ...23 5 Dimensions 5 1 Indoor Unit ...
Page 24: ...24 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 25: ...25 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 27: ...27 ...
Page 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 30: ...30 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 31: ...31 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 35: ...35 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...
Page 40: ...40 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 42: ...42 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 66: ...66 Solar Priority is Set Solar Priority is Not Set ...
Page 69: ...69 Heat Tank Heating No Priority Solar Priority Set ...
Page 70: ...70 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 80: ...80 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 81: ...81 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 129: ...129 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 130: ...130 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 155: ...155 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 158: ...158 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 159: ...159 ...
Page 162: ...162 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 163: ...163 ...