Case 2:
• Heat pump THERMO OFF TEMP:
1. Heat pump THERMO OFF TEMP = 55
°
C +
[+2
°
C]
.
2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 90 seconds, switch 3 ways valve to room
side. End Tank heat-up interval and start count heating heat-up interval.
• THERMO ON TEMP:
1. THERMO ON TEMP = Tank temp. when heatpump thermo off +
[-3
°
C]
.
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval when tank
temperature < THERMO ON TEMP.
Case 3:
• Heat pump THERMO OFF TEMP:
1. Water inlet temperature > X_INLETDT_1
°
C for continuous X_INLETDT_2 sec, switch 3 ways valve to room side. End
tank heat-up interval and start count heating heat-up interval.
• THERMO ON TEMP:
1. THERMO ON TEMP = Tank temp. when heatpump thermo off +
[-3
°
C]
.
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval when tank
temperature < THERMO ON TEMP.
Case 4: (Only during solar priority is set condition)
• When solar pump ON, tank heat-up interval end early and 3 ways valve switch to room side.
• THERMO ON TEMP:
1. THERMO ON TEMP = Heat pump tank target tempe
[-3
°
C]
.
2. After Heating heat-up interval, always detect tank temperature. Switch to next tank heat-up interval when tank
temperature < THERMO ON TEMP. and solar 3 way valve OFF.
3. Backup heater control:
a. During heating heat up interval
• Follow normal backup heater control operation
b. During tank heat-up interval
• Backup heater OFF during this interval
4. Booster heater control:
a. During heating heat-up interval.
• Booster heater ON/OFF according to booster heater operation control
b. During tank heat-up interval.
• Once switch from heating heat-up interval to tank heat-up interval, turn off the booster heater and start counting the
BOOSTER HEATER DELAY TIMER.
• Booster heater turn ON after BOOSTER HEATER DELAY TIMER fufil and tank temperature lower than tank set
temperature.
• BOOSTER HEATER DELAY TIMER is clear when switch to heating heat-up interval.
5. Solar 3 way valve
• Solar 3WV operates follow solar operation specification.
* Under solar priority is set condition, when solar 3WV is ON, booster heater turn OFF
* Under solar priority is not set condition, solar 3WV only can ON during heating heat-up interval.
6. 2 ways valve control:
• 2 ways valve opens.
Summary of Contents for WH-SDC07C3E5
Page 17: ...17 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Page 18: ...18 ...
Page 19: ...19 ...
Page 20: ...20 4 1 2 Weekly Timer Setting ...
Page 21: ...21 4 1 3 Setting Up The Special Functions ...
Page 22: ...22 4 1 4 Main Components 4 2 Outdoor Unit ...
Page 23: ...23 5 Dimensions 5 1 Indoor Unit ...
Page 24: ...24 5 2 Outdoor Unit 5 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 25: ...25 5 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 27: ...27 ...
Page 28: ...28 7 Block Diagram 7 1 WH UD07CE5 A WH UD09CE5 A ...
Page 29: ...29 7 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 30: ...30 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 31: ...31 8 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 32: ...32 8 2 Outdoor Unit 8 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 33: ...33 8 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 34: ...34 9 Electronic Circuit Diagram 9 1 Indoor Unit 9 1 1 WH SDC07C3E5 WH SDC09C3E5 ...
Page 35: ...35 9 1 2 WH SDC12C6E5 WH SDC14C6E5 WH SDC16C6E5 ...
Page 36: ...36 9 2 Outdoor Unit 9 2 1 WH UD07CE5 A WH UD09CE5 A ...
Page 37: ...37 9 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 38: ...38 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 39: ...39 10 1 2 Solar Printed Circuit Board Optional ...
Page 40: ...40 10 2 Outdoor Unit 10 2 1 WH UD07CE5 A WH UD09CE5 A 10 2 1 1 Main Printed Circuit Board ...
Page 41: ...41 10 2 1 2 Capacitor Printed Circuit Board 10 2 1 3 Noise Filter Printed Circuit Board ...
Page 42: ...42 10 2 2 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A 10 2 2 1 Main Printed Circuit Board ...
Page 43: ...43 10 2 2 2 Capacitor Printed Circuit Board 10 2 2 3 Noise Filter Printed Circuit Board ...
Page 66: ...66 Solar Priority is Set Solar Priority is Not Set ...
Page 69: ...69 Heat Tank Heating No Priority Solar Priority Set ...
Page 70: ...70 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 80: ...80 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 81: ...81 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 129: ...129 18 3 To Remove Pressure Gauge 18 4 To Remove Control Panel ...
Page 130: ...130 18 5 To Remove RCCB 18 6 To Remove Transformer and Electronic Controller Board ...
Page 155: ...155 19 4 Hydraulic Pump Performance 07C3 09C3 12C6 14C6 16C6 ...
Page 158: ...158 20 2 WH UD07CE5 A WH UD09CE5 A ...
Page 159: ...159 ...
Page 162: ...162 20 3 WH UD12CE5 A WH UD14CE5 A WH UD16CE5 A ...
Page 163: ...163 ...