86
16.3 Breakdown Self Diagnosis Function
16.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code)
When abnormality occur during operation, the system will stop operation, and OFF/ON remote control LED will
blink and error code will display on the remote control Timer display LCD.
Even error code is reset by turning OFF power supply or by pressing ERROR RESET button, if the system
abnormality is still un-repaired, system will again stop operation, and OFF/ON remote control LED will again blink.
The error code will store in IC memory.
To check the error code
1. When an abnormality occurs, system will stop operation and OFF/ON remote control LED will blink.
2. Error code of the abnormality will display on the remote control Timer display LCD.
3. To determine the abnormality description, the Error Code Table needs to be referred.
To display past/last error code
1. Turn ON power supply.
2. Press and hold the CHECK button for more than 5 seconds to enter status mode.
3. Press the SEARCH DOWN/UP button to retrieve past/last error code.
4. Press the CANCEL button or wait 30 seconds to exit status mode.
To permanently delete error code from IC memory
1. Turn ON power supply.
2. Press and hold the ERROR RESET button for more than 8 seconds till a beep sound is heard.
COOL
CANCEL
Button
SEARCH
Downward/Upward
Button
CHECK
Button
ERROR
RESE T
Button
Summary of Contents for WH-MHF09G3E8
Page 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Page 33: ...33 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 34: ...34 10 2 1 1 Noise Filter Printed Circuit Board ...
Page 47: ...47 Heat Mode Operation Time Chart ...
Page 49: ...49 ...
Page 50: ...50 ...
Page 56: ...56 ...
Page 57: ...57 ...
Page 58: ...58 ...
Page 127: ...127 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 138: ...138 19 2 Water System 44 46 17 16 4 34 42 18 43 3 33 9 1 45 45 47 2 35 48 36 19 ...