33
11.1 Select the Best Location
Install the Mono bloc unit in outdoor locations only.
Avoid installations in areas where the ambient
temperature may drop below -20°C.
The Mono bloc unit must be installed on a flat,
solid surface.
A place removed from any heat source or steam
which may effect the operation of the Mono bloc
unit.
A place where air circulation is good.
A place where drainage can be easily done.
A place where Mono bloc unit’s operation noise
will not cause discomfort to the user.
A place which is accessible for maintenance.
Ensure to keep minimum distance of spaces as
illustrated below from wall, ceiling, or other
obstacles.
A place where flammable gas leaking might not
occur.
A place where the Mono bloc unit’s piping and
wiring lengths come within reasonable ranges.
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
Do not place any obstacles which may cause a
short circuit of the discharged air.
Avoid installing the Mono bloc unit at a location
where suction side may be exposed directly to
wind.
If Mono bloc unit installed near sea, region with
high content of sulphur or oily location (e.g.
machinery oil, etc.), it lifespan maybe shorten.
When installing the product in a
place where it will be affected by
typhoon or strong wind such as
wind blowing between buildings,
including the rooftop of a building
and a place where there is no
building in surroundings, fix the
product with an overturn prevention
wire, etc. (Overturn prevention
fitting model number: K-KYZP15C)
When connecting solar pump station cable
between Mono bloc unit and solar pump station,
the distance between both apparatuses shall be
2 ~ 8 meters and the length of the said cable must
be shorter than 10 meter.
Failure to do so may lead to abnormal operation
to the system.
11.2 Mono Bloc Unit Installation
Mono bloc unit will become heavy when filled with
water. Please install the unit on a strong concrete floor
and consider the weight of the unit and water.
Fix Mono bloc unit on the concrete floor with M12
anchor bolt at 4 locations.
Pull-out strength of these anchor bolts must be
above 15000N.
Summary of Contents for WH-MDF12C6E5
Page 12: ...12 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 4 1 1 Main Components ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 4 1 3 Weekly Timer Setting ...
Page 18: ...18 4 1 4 Setting Up The Special Functions ...
Page 19: ...19 5 Dimensions 5 1 Mono bloc Unit ...
Page 20: ...20 6 Refrigeration and Water Cycle Diagram ...
Page 21: ...21 ...
Page 22: ...22 7 Block Diagram ...
Page 23: ...23 8 Wiring Connection Diagram ...
Page 24: ...24 ...
Page 25: ...25 9 Electronic Circuit Diagram ...
Page 26: ...26 ...
Page 27: ...27 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 31: ...31 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 32: ...32 Main Components ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 ...
Page 107: ...107 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 115: ...115 ...