62
13.1.6 Low Pressure Protection Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 5 minutes.
Detection
conditions:
o
When detection of Tem above 30°C.
o
Calculation of average evaporation temperature (Tem).
o
Use outdoor low pressure sensor.
o
Tem use the value calculated for discharge temperature setting value.
After
detection:
o
Compressor stops restart again after 3 mins.
o
When abnormalities continuously generated 60 times within 480 minutes.
o
Protection
is
prohibited.
o
Error H42 will be displayed.
13.1.7 High Pressure Sensor Control
Purpose:
o
To protect the system operation.
Detection
period:
o
After compressor on for 1 minute.
Detection
conditions:
o
When abnormal high voltage detection, 5V or when open circuit detection 0V for 5 seconds continuously.
After
detection:
o
When abnormality is detected continue 5 seconds, unit stop operation.
o
OFF/ON remote control LED will blink (H64 error occurs).
13.1.8 Outside Temperature Current Control
13.1.9 Extreme Low Temperature Control
Purpose:
- To improve the compressor reliability during cold start and after deice when running in extreme low outdoor
temperature -20°C.
Starting
condition:
o
Heating
operation
o
Outdoor air temperature < -10°C
o
Actual
frequency
≥
50Hz
o
Compressor discharge temperature < 20°C
When the above condition is fulfilled, this control is activated.
5Hz up every 30 sec. until it reaches the target frequency.
Cancellation
condition:
o
starting condition not fulfill.
o
Cancel the extreme low temperature control when compressor discharge sensor
≥
60°C
Summary of Contents for WH-MDF12C6E5
Page 12: ...12 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 4 1 1 Main Components ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 4 1 3 Weekly Timer Setting ...
Page 18: ...18 4 1 4 Setting Up The Special Functions ...
Page 19: ...19 5 Dimensions 5 1 Mono bloc Unit ...
Page 20: ...20 6 Refrigeration and Water Cycle Diagram ...
Page 21: ...21 ...
Page 22: ...22 7 Block Diagram ...
Page 23: ...23 8 Wiring Connection Diagram ...
Page 24: ...24 ...
Page 25: ...25 9 Electronic Circuit Diagram ...
Page 26: ...26 ...
Page 27: ...27 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 31: ...31 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 32: ...32 Main Components ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 ...
Page 107: ...107 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 115: ...115 ...