61
13. Protection
Control
13.1 Protection Control For All Operations
13.1.1 Time Delay Safety Control
1 The compressor will not start for three minutes after stop of operation.
13.1.2 30 Seconds Forced Operation
1 Once the compressor starts operation, it will not stop its operation for 30 seconds.
2 However, it can be stopped using remote control.
13.1.3 Total Running Current Control
1 When the mono bloc unit running current exceeds X value, the compressor frequency will decrease.
2 If the mono bloc unit running current does not exceed X value, the compressor frequency will return to
normal operating frequency.
3 If the mono bloc unit running current continue to increase till exceed Y value, compressor will stop, and if this
occurs 3 times within 20 minutes, system will stop operation and OFF/ON remote control LED will blink (F16
error occurs).
09C 12C 14C 16C
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Heating
22.7 27.9 24.0 27.9 25.0 27.9 26.0 27.9
13.1.4 IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1 When the IPM temperature rises to 95°C, compressor will stop immediately.
2 Compressor will restart delay 3 minutes when the IPM temperature decreases to 90°C.
If this condition repeats continuously 3 times within 30 minutes, system will stop operation and OFF/ON
remote control LED will blink (F22 error occurs).
B. DC Peak Current Control
1 When the current to IPM exceeds set value of 40.1 ± 5.0 A (MDF09C), 44.7 ± 5.0 A (MDF12C, MDF14C,
MDF16C), compressor will stop. Compressor will restart after three minutes.
2 If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart
after two minutes.
3 If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after
one minute. If this condition repeats continuously for seven times, system will stop operation and OFF/ON
remote control LED will blink (F23 error occurs).
13.1.5 Compressor Overheating Prevention Control
The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in
below figures. When the compressor tank temperature exceeds 112°C, compressor will stop, and if this occurs 4
times within 30 minutes, system will stop operation and OFF/ON remote control LED will blink (F20 error occurs).
Summary of Contents for WH-MDF12C6E5
Page 12: ...12 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 4 1 1 Main Components ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 4 1 3 Weekly Timer Setting ...
Page 18: ...18 4 1 4 Setting Up The Special Functions ...
Page 19: ...19 5 Dimensions 5 1 Mono bloc Unit ...
Page 20: ...20 6 Refrigeration and Water Cycle Diagram ...
Page 21: ...21 ...
Page 22: ...22 7 Block Diagram ...
Page 23: ...23 8 Wiring Connection Diagram ...
Page 24: ...24 ...
Page 25: ...25 9 Electronic Circuit Diagram ...
Page 26: ...26 ...
Page 27: ...27 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 31: ...31 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 32: ...32 Main Components ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 ...
Page 107: ...107 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 115: ...115 ...