52
12.3 Pump Down Operation
Purpose
Ensure the pump down operation when relocating or disposing of the unit. The pump down operation will extract all
refrigerant from the piping into the mono bloc unit.
Pump down operation control:
1 Press the SERVICE S/W for continuous 5 secs to enter Service mode.
2 In service mode, select Sr:01 and press SET S/W to start Pump Down operation.
3 There will be no Low Pressure error & Freeze prevention judgement during pumpdown operation.
4 3 ways valve will shift to room side.
5 Press the ON/OFF button to stop the unit.
12.4 Flow
Switch
12.4.1 Flow Switch Control
1 The water flow switch serve as an overload protector that shuts down the unit when the water level is
detected to be low.
2 Detection is Lo (0V) when there is no water flow, and detection is Hi (5V) when there is water flow.
12.5 Force Heater Mode Operation
The backup heater also serves as backup in case of malfunctioning of the mono bloc unit.
1 Make sure the OFF/ON remote control LED is OFF (no operation).
2 Press the Force button to start the force heater mode operation.
3 During force heater mode, all other operations are not allowed.
4 Press OFF/ON button to stop the force heater mode operation.
Summary of Contents for WH-MDF12C6E5
Page 12: ...12 4 Location of Controls and Components 4 1 Mono bloc Unit ...
Page 13: ...13 4 1 1 Main Components ...
Page 15: ...15 ...
Page 16: ...16 ...
Page 17: ...17 4 1 3 Weekly Timer Setting ...
Page 18: ...18 4 1 4 Setting Up The Special Functions ...
Page 19: ...19 5 Dimensions 5 1 Mono bloc Unit ...
Page 20: ...20 6 Refrigeration and Water Cycle Diagram ...
Page 21: ...21 ...
Page 22: ...22 7 Block Diagram ...
Page 23: ...23 8 Wiring Connection Diagram ...
Page 24: ...24 ...
Page 25: ...25 9 Electronic Circuit Diagram ...
Page 26: ...26 ...
Page 27: ...27 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 28: ...28 10 1 2 Solar Printed Circuit Board Optional ...
Page 29: ...29 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 30: ...30 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 31: ...31 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Page 32: ...32 Main Components ...
Page 42: ...42 ...
Page 48: ...48 ...
Page 49: ...49 ...
Page 59: ...59 ...
Page 107: ...107 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 115: ...115 ...