61
12.5. Force Heater Mode Operation
The backup heater also serves as backup in case of malfunctioning of the Monobloc unit.
1. Make sure the OFF/ON control panel LED is OFF (no operation).
2. Press the Force button to start the force heater mode operation.
3. During force heater mode, all other operations are not allowed.
4. Press OFF/ON button to stop the force heater mode operation.
12.6. Monobloc Unit Safety
12.6.1.
Monobloc Unit Safety Control
1. When water pump is ON, the system will start checking flow switch status (ON/OFF).
2. If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80
°
C, the water pump shall be continuously running with normal mode.
If the water inlet temperature exceeds 80
°
C for continuously 10 seconds, the water pump will be OFF immediately.
3. After water pump OFF for more than 10 minutes, it will be ON back and the Monobloc unit safety control checking is restarted.
12.7. Auto Restart Control
1. When the power supply is cut off during the operation of Monobloc unit, the compressor will re-operate after power supply
resumes.
Summary of Contents for WH-MDC09C3E5
Page 14: ...14 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 2 2 Weekly Timer Setting ...
Page 20: ...20 4 1 2 3 Setting Up The Special Functions ...
Page 21: ...21 5 Dimensions 5 1 Monobloc Unit ...
Page 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH MDC09C3E5 ...
Page 25: ...25 7 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 WH MDC09C3E5 ...
Page 27: ...27 ...
Page 28: ...28 8 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 29: ...29 ...
Page 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDC09C3E5 ...
Page 31: ...31 ...
Page 32: ...32 9 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 33: ...33 ...
Page 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Page 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 37: ...37 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 38: ...38 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 39: ...39 Main Components ...
Page 52: ...52 Solar Priority is Set Solar Priority is Not Set ...
Page 55: ...55 Heat Tank Heating No Priority Solar Priority Set ...
Page 56: ...56 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 66: ...66 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 67: ...67 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 115: ...115 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 130: ...130 ...
Page 134: ...134 19 2 WH MDC09C3E5 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 Water System ...