12.10. Tank Booster Heater Control
12.10.1. Tank booster heater control
Heating operation condition:
1. Booster heater Turn On condition:
• After BOOSTER HEATER DELAY TIMER fulfil during heat pump startup time in tank mode, or during switching from heating
heat-up interval to tank heat-up interval in heat+tank mode (heating priority not set).
• Tank temperature < tank set tempe
[-5
°
C]
,
• 20 minutes since previous heater off.
* BOOSTER HEATER DELAY TIMER is clear when tank heat-up interval end.
2. Booster heater Turn Off condition:-
• Tank temperature > tank set tempe
[+2
°
C]
for continuous 15 sec
• When BOOSTER HEATER DELAY TIMER start count after switch from heating heat-up interval to tank heat-up interval
* DELAY TIMER can be set by control panel.
12.11. Three Way Valve Control
• Purpose:
- 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side
• Control contents:
1. 3 ways valve switch Off:
• During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side.
2. 3 ways valve switch On:
• During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
3. Stop condition:
• During stop mode, 3 ways valve will be in switch off position
12.12. Sterillization Mode
1. During Sterillization mode, Tank will be heat up to the Sterillize Set temperature for a certain period of time, also set by
controller.
2. The function can only be set on timer to operate once in a week.
3. It will be cancelled even when the temperature is not reached after 4 hours.
4. When tank mode is OFF or disabled, sterillization is cancelled.
Summary of Contents for WH-MDC09C3E5
Page 14: ...14 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 2 2 Weekly Timer Setting ...
Page 20: ...20 4 1 2 3 Setting Up The Special Functions ...
Page 21: ...21 5 Dimensions 5 1 Monobloc Unit ...
Page 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH MDC09C3E5 ...
Page 25: ...25 7 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 WH MDC09C3E5 ...
Page 27: ...27 ...
Page 28: ...28 8 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 29: ...29 ...
Page 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDC09C3E5 ...
Page 31: ...31 ...
Page 32: ...32 9 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 33: ...33 ...
Page 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Page 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 37: ...37 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 38: ...38 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 39: ...39 Main Components ...
Page 52: ...52 Solar Priority is Set Solar Priority is Not Set ...
Page 55: ...55 Heat Tank Heating No Priority Solar Priority Set ...
Page 56: ...56 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 66: ...66 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 67: ...67 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 115: ...115 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 130: ...130 ...
Page 134: ...134 19 2 WH MDC09C3E5 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 Water System ...