43
How to guide cable / cord to bushing
Connecting with external device (optional)
1. All connections shall follow to the local national wiring
standard.
2. It is strongly recommended to use manufacturer-
recommended parts and accessories for installation.
3. Maximum output power of booster heater should be 3
kW. Booster Heater’s cord must be (3
×
min 1.5 mm
2
), of
type designation 60245 IEC 57 or heavier.
4. Two-Way Valve shall be spring and electronic type, refer
to “Field Supply Accessories” table for details. Valve’s
cable shall be (3
×
min 0.5 mm
2
), of type designation
60245 IEC 57 or heavier, or similarly double insulation
sheathed cable.
* note: - Two-Way should be CE marking compliance
component.
- Maximum load for the valve is 3VA.
5. Three-Way Valve shall be spring and electronic type.
Valve’s cable shall be (3
×
min 0.5 mm
2
), of type
designation 60245 IEC 57 or heavier, or similarly double
insulation sheathed cable.
* note: - Shall be CE marking compliance component.
- It shall be directed to heating mode when it is
OFF.
- Maximum load for the valve is 3VA.
6. Receiver shall be connected to “Room Thermostat”, refer
to “Field Supply Accessories” table for details. Receiver’s
cable must be (4 or 3
×
min 0.5 mm
2
), double insulation
layer of PVC-sheathed or polychloroprene sheathed
cable. (connection refer to Diagram 4.2).
7. Tank OLP’s cable must be (2
×
min 0.5 mm
2
), double
insulation layer of PVC-sheathed or polychloroprene
sheathed cable.
* note: - if such connection deemed NO necessary for
tank OLP, please connect jumper between
terminal no #13 and #14.
8. Tank Sensor shall be resistance type, please refer to
Graph 4.1 for the characteristic and details of sensor. Its
cable shall be (2
×
min 0.3 mm
2
), double insulation layer
(with insulation strength of min 30V) of PVC-sheathed or
polychloroprene sheathed cable.
9. External Controller shall be connected to 1-pole switch
with min 3.0mm contact gap. (connection refer to
Diagram 4.3). Its cable must be (2
×
min 0.5 mm
2
),
double insulation layer of PVC-sheathed or
polychloroprene sheathed cable.
* note: - When making such connection, kindly remove
the jumper between terminal no #17 and #18.
- Switch used shall be CE compliance component.
- Maximum operating current shall be less than
3A
rms
.
10. Solar Three-way Valve’s cable shall be (3
×
min 0.5
mm
2
), double insulation layer PVC-sheathed or polychlo-
roprene sheathed cable.
11. Must install Solar Connection PCB to Mono bloc unit
when Solar Pump Station is utilized. Refer Solar Connec-
tion PCB’s installation instruction for detail of installation.
12. Solar Pump Station’s cable shall be (2
×
min 0.5 mm
2
), of
double insulation PVC-sheathed or polychloroprene
sheathed cable. Strongly recommended install with
maximum length of 10 meter only.
Summary of Contents for WH-MDC09C3E5
Page 14: ...14 4 Location of Controls and Components 4 1 Monobloc Unit ...
Page 17: ...17 ...
Page 18: ...18 ...
Page 19: ...19 4 1 2 2 Weekly Timer Setting ...
Page 20: ...20 4 1 2 3 Setting Up The Special Functions ...
Page 21: ...21 5 Dimensions 5 1 Monobloc Unit ...
Page 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Page 23: ...23 ...
Page 24: ...24 7 Block Diagram 7 1 WH MDC09C3E5 ...
Page 25: ...25 7 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 26: ...26 8 Wiring Connection Diagram 8 1 WH MDC09C3E5 ...
Page 27: ...27 ...
Page 28: ...28 8 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 29: ...29 ...
Page 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDC09C3E5 ...
Page 31: ...31 ...
Page 32: ...32 9 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Page 33: ...33 ...
Page 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Page 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Page 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Page 37: ...37 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Page 38: ...38 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Page 39: ...39 Main Components ...
Page 52: ...52 Solar Priority is Set Solar Priority is Not Set ...
Page 55: ...55 Heat Tank Heating No Priority Solar Priority Set ...
Page 56: ...56 Heat Tank Heating No Priority Solar Priority Not Set ...
Page 66: ...66 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Page 67: ...67 Tank Mode Solar Priority Set Solar Priority Not Set ...
Page 115: ...115 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Page 130: ...130 ...
Page 134: ...134 19 2 WH MDC09C3E5 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 Water System ...