Vinyl tape (Wide)
Saddle
Indoor/Outdoor connecting cable
6-CORE WIRE min 1.5mm
2
Type designation 60245 IEC 57 or heavier cord
ø15.88mm (5/8") Gas refrigerant piping
ø9.52mm (3/8") Liquid refrigerant piping
100mm
or more
1000mm
or more
100mm
or more
300mm
or more
SELECT THE BEST LOCATION
1
INSTALL THE OUTDOOR UNIT
2
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.
Avoid installations in areas where the ambient temperature may drop below -28°C.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If outdoor unit installed near sea, region with high content of sulphur or oily location (e.g. machinary oil, etc.), it lifespan maybe shorten.
When installing the product in a place where it will be affected by typhoon or strong wind such as wind blowing between
buildings, including the rooftop of a building and a place where there is no building in surroundings, fi x the product with an
overturn prevention wire, etc. (Overturn prevention fi tting model number: K-KYZP15C)
If piping length is over 10 m, additional refrigerant should be added as shown in the table.
Piping size
Rated
Length
(m)
Max.
Elevation
(m)
Min. Piping
Length
(m)
Max. Piping
Length
(m)
Additional
Refrigerant
(g/m)
Gas
Liquid
ø15.88mm (5/8") ø9.52mm (3/8")
7
20
3
30
50
Example:
If piping length is 30m, the quantity of additional refrigerant should be 1000g. [(30-10)m x 50 g/m = 1000g]
GWP (R410A) = 2088
INSTALLATION DIAGRAM
DIMENSION DIAGRAM
•
It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation,
please consult authorized dealer/specialist.
•
This illustration is for explanation purposes only.
(Unit : mm)
148
31
28
44
60
156
20
70
157
152
152
356
980
189
426.5
615
1284
322
39
59
322
400
419
318.5
1410