3WAY SYSTEM
Trouble Diagnosis
4. 3WAY Alarm Codes
With types 8HP and 10HP, the INV compressor is compressor 1.
With types 12HP, 14HP and 16HP, the INV compressor is compressor 1, and the constant-speed
compressors (AC1) are compressors 2.
Page
Alarm meaning
Alarm code
5
-8
5
-8
5
-8
5
-9
5
-9
5
-9
5
-10
5
-10
E06
E12
E15
E16
E20
E24
E25
E26
E29
Outdoor unit failed to receive serial communication signals from indoor unit.
Automatic address setting start is prohibited.
Automatic address setting alarm (too few units)
Automatic address setting alarm (too many units)
No indoor units at automatic address setting.
Outdoor unit failed to receive communications from another outdoor unit.
Outdoor unit address setting failure (duplication)
Mismatch in outdoor unit quantity
Outdoor unit failed to receive communication from outdoor unit (main)
5
-10
E31
Communication error between the microcomputers
5
-10
F04
5
-11
F05
5
-11
-12
F16
5
-14
F17
5
-15
F23
5
-12
F24
5
-12
F31
Compressor 1 discharge temperature sensor trouble
Compressor 2 discharge temperature sensor trouble
F06
5
F07
5
-12
F08
5
-13
F12
5
-13
5
-13
Gas temperature sensor trouble at outdoor heat exchanger 1 (In)
Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)
Outdoor air temperature sensor trouble
Compressor intake temperature sensor trouble (SCT)
F14
Temp. sensor at refrigerant gas outlet of dual-tube (SCG)
High pressure sensor failure. High pressure trouble.
Low-pressure sensor trouble
Gas temperature sensor trouble at outdoor heat exchanger 2 (In)
Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)
Outdoor unit non-volatile memory (EEPROM) trouble
5
-15
H01
Compressor 1 current trouble
5
-15
5
-16
5
-16
5
-17
5
-17
5
-18
H11
H12
H03
H05
H06
Constant speed compressor 2 overcurrent alarm
Constant speed compressor 2 lock current alarm
Compressor 1 CT sensor disconnected or short-circuit
Compressor 1 discharge temperature sensor disconnected
Low-pressure switch activated
5
-19
5
-17
5
-17
5
-19
H08
H13
H15
H27
H31
Compressor 1 oil detection sensor (connection) trouble
Compressor 2 CT sensor disconnected or short-circuit
Compressor 2 discharge temperature sensor disconnected
Compressor 2 oil detection sensor (connection) trouble
HIC trouble alarm
5
-19
5
-19
5
-20
5
-20
Outdoor system address duplication
Outdoor unit capacity not set
Incorrect wiring of remote group control wiring (in case of shared solenoid valve kit)
Outdoor unit model mismatch
5
-21
L04
L10
L11
L17
5
-21
Compressor thermal protector is activated. (trip only and no alarm)
P02
5
-22
5
-23
5
-23
P03
P04
P05
Compressor 1 discharge temperature trouble
High-pressure switch activated
Reverse phase (or missing phase) detected
5
-24
P14
O
2
sensor (detects low oxygen level) activated
5
-24
5
-22
P16
P17
Compressor 1 (INV) overcurrent
Compressor 2 discharge temperature trouble
5
-25
P22
Fan motor trouble
P29
Inverter compressor missing phase or lock alarm
5
-25
Blinking Inspection Display on the remote
controller
CHECK blinking (1)
5
-26
CHECK blinking (2)
5
-27