3WAY SYSTEM
Outdoor Unit Maintenance Remote Controller
3
- 12
3
6. Mode Settings
N
Setting mode 1
<Operating procedure>
Press and hold the
(CHECK) button and
(VENTILATION) button simultaneously for 4
seconds or longer.
Use the temperature setting
and
buttons to change the item code. The item codes
and setting data are shown in the table below.
Use the timer time
and
buttons to change
the setting data.
To confirm the changed setting data, press the
button.
(At this time, “
” stops blinking and remains
lit.)
During this mode, “
” is displayed, blinking.
The outdoor unit address display section displays
“ALL,” the item code number (DN value in the
table), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The
display changes between the first 4 digits (Fig.
A
)
and the last 4 digits (Fig.
B
). When the first 4
digits are displayed, the bottom dot of the colon is
lit.)
To exit the setting mode, press the
(CHECK)
button.
1
2
3
5
5
3
1
2
A
and
B
are displayed alternately.
(Example shows display of 0000 0001.)
A
Display of first 4 digits
B
Display of last 4 digits
DN
Parameter
Description
Snowfall sensor usage
0 = Sensor input not present. Control is performed.
1 = Sensor input present. Control is performed.
2 = Sensor input not present. Control is not performed.
3 = Sensor input present. Control is not performed.
Outdoor unit fan Quiet
mode
0 = Disabled
1 = Quiet mode 1
2 = Quiet mode 2
3 = Quiet mode 3
4 = Quiet mode 4
Energy saving mode
0 = None
1 = Discharge temp. control only (Mode 3)
2 = Demand only (Mode 2)
3 = Discharge temp. c Demand (Mode 1)
Energy saving operation
plug
0 = Independent
1 = All indoor units linked
Demand 1 current
0 = 0% 1 = 40 … 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
Demand 2 current
0 = 0% 1 = 40 … 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
High static pressure mode
0 = Disabled
6 = High static pressure mode
* Charge when the external static pressure is increased to over 30 Pa.