1
- 51
3WAY SYSTEM
Control Functions
1
14. Detail setting in EEPROM of outdoor unit
DN
Item
Setting No.
Never use the DN code unlisted in the following table.
(P) : Factory preset mode
A3
The minimum operating time 1 until defrosting
20=20min..
21=21min. ,,,,,
40=40min. (P)
(For detail, refer to 9-2)
41 - 90=Never use
1=Valid
A6
Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Valid
A7
Validity/invalidity of capacity control when cooling
operation
0=Invalid (P)
1=Valid
AC
Actuation of solenoid valve kit (EP closed)
0=Invalid (P)
C1
O2 output change
0=Continuously set OFF (P)
1=Refrigerant leak prevention (normal OFF)
2=Refrigerant leak prevention (normal ON)
(For detail, refer to 4-7)
(For detail, refer to 6-5)
E1
-20=-20 min.
0=0 min. (P) ,,,,,
10=10 min.
-19=-19 min. ,,,,,
Discharge air temperature control with thermostat
OFF additional time
SM830226-00̲3WAY ECO-i SYSTEM.in51 51