3WAY SYSTEM
Control Functions
1
5. Outdoor Fan Control
5-1. Fan mode
These outdoor units utilize a DC fan motor that can be controlled in a maximum of 15 steps (15 modes).
However, fan modes 14 and 15 can only be used if high static pressure mode has been set.
* For information concerning EEPROM settings, refer to the field application functions.
* For the sake of protecting temperature of the electrical parts, the minimum values of the fan mode may sometimes
increase in accordance with the ambient temperature or the amount of secondary current.
The following table shows the maximum and minimum fan mode and fan forced mode for each unit.
Standard
Condenser
Evaporator
> 10°C
Ambient
temperature
> 10°C
Ambient
temperature
<
_ 10°C
Ambient
temperature
<
_ 10°C
Ambient
temperature
Condenser
Evaporator
Snowfall sensor control
Silent mode 1 (-3dBA)
Silent mode 2 (-5dBA)
Control for fan crack prevention
Fan forced mode
Status of
heat exchanger
High static
pressure mode
setting
Silent mode
Maximum value
Minimum value *
16hp
12
12
13
12
12
13
7
8
8
9
14hp
12
12
13
12
12
13
7
8
8
9
12hp
13
13
13
15
15
15
8
9
9
10
10hp
13
13
13
15
15
15
1
1
1
1
9
10
7
8
8hp
13
13
13
15
15
15
1
9
11
7
9
5-1-1. High Static Pressure Mode
The outdoor unit allows a high static pressure changing the settings.
The maximum permissible static pressure is 80Pa.
CODE : 8F
However, maximum fan mode is upper limit.
Setting No
0
1
2
3
4
5
6
Invalid (factory preset mode)
High static pressure mode
Never use
Never use
Never use
Never use
Never use
EEPROM setting in each outdoor unit
SM830226-00̲3WAY ECO-i SYSTEM.in19 19