$D!$@

The diagram shows operation with safety outputs 1 / 2 in auto-reset 
mode.

Light
received
Light
blocked

Light curtain

ON

OFF

ON

OFF

ON

OFF

Safety output 2
(34 and 44)

Muting sensor 1

ON

OFF

Auxiliary output 1
(Muting output)

ON

OFF

Auxiliary output 3
(Blown lamp output)

Muting lamp 
output 1

Blown
lamp

ON

OFF

Muting sensor 2

Muting lamp 
output 2

ON

OFF

Blown
lamp

Blown
lamp

 

 The lamps are monitored during muting state, and if either of them 

blows, auxiliary output 3 is turned OFF. If only one lamp blows, the 
muting state is maintained, however, if both lamps blow, the muting 
state is canceled immediately.

11

FUNCTIONS

WARNING

 

 Incorrect using of the muting control may cause an accident. 

Please understand the muting control fully, and use it. As for the 
    -
quirements.
<!\>][_*\;"^_`[*\Z‡<|_ˆX`*\6
“Safety of machinery - Safety-related parts of control systems - 
?\‰    `_7 Š
<"0Y\[_Y*\;:Y\[_Y*\Z"^Y\[_Y*\Z‡<|_ˆX[*\6
“Safety of machinery - Electro sensitive protective equipment - Part 
\‰= &ˆ7 Š
<"0YXRX[*\;‡<|__YX*\6
‹    * "  =     * ? \
General requirements, 9.2.4 Overriding safeguards”
"^[\`*[
‹  '    * ? [ ? Œ  -
izers, Annex A, A2.2 Muting”
^<|\\\_*\__X
“for Machine Tools-Safeguarding When Referenced by the Other 
B11 Machine Tool Safety Standards-Performance Criteria for the 
 0 0! Š[R>?*-
 % "*! { †=;{†6
^<Z{<{\`XY*\___
“for Industrial Robots and Robot Systems - Safety Requirements, 
10.4.5 Muting”

 

 Use the muting control while the machine cycle is not in danger 

mode. Maintain safety with the other measures while the muting 
control is activating.

 

 For the application that the muting control is activated when a 

workpiece passes through the sensor, place the muting sensor so 
          #   #  -
sion of personnel when the workpiece is passing through the sen-
sor or the workpiece is not passing through it.

 

 The muting lamp should be installed in a position where it can al-

ways be seen by operators who set or adjust the machine.

 

 Be sure to check the operation of the muting function before its 

use. Furthermore, check the state of the muting lamp (cleanliness, 
brightness, etc.)

 

 This product cannot be used in combination with the handy control-

ler 

:

 

Reset operation

WARNING

           #  
outside the dangerous area, and also where the operators can see 
the entire dangerous area.

The reset function corresponding to the respective safety outputs 1 
/ 2 / 3 is incorporated.
€\\€\R€\> {  \

€\\€\R 7
€\\€\> *

€R\€RR€R> {  R

€R\€RR 7
€R\€R> *

€>\€>R {  >

(Manual reset only).

However, if the muting function is valid, safety output 2 is not turned OFF.

 

Safety output 1

This is the output corresponding to light curtain in light received / 
light blocked status.
<  %!^< #'!††
However, if the emergency stop is valid, safety output 1 is OFF.

 

+H

This is the output corresponding to the light curtain in light received 
/ light blocked status including the muting state.
<  %    % !^
< #'     % !††
However, if the emergency stop is valid, the safety output 2 is OFF.

 

Safety output 3

This is the output corresponding to the external emergency stop switch.
  % !^
 % !††
However, if the emergency stop is valid, both safety outputs 1 / 2 are OFF.

^  !^ !††  *

   ;!†† \XX‘6!†† -
nal is fedback, it is judged that the circuit works properly. When the OFF signal is 
not fedback, it is judged that the output circuit or wiring is in error and the safety 
output is maintained in the OFF state.

WARNING

Please consider the input response time of the machine to which you 
connect this product so that no malfunction occurs due to this prod-
uct's OFF signal.

 

Emergency stop

Safety output 3 can be controlled by connecting an external emer-
gency stop switch or another interlock device.
„|R^0 #  

 

Test input

WARNING

               
machine in which the light curtain is installed. Failure to do so could 
result in death or serious injury.

This function turns safety outputs 1 / 2 OFF forcibly. 
!#+\+R † #!††
*  #+\+R ^
This is used when the override function is used as well. 

 

Muting function

This function turns the safety output 2 into invalid temporarily. This 
function is available for passing the workpieces through the sensing 
area of the light curtain without stopping the machine.
The muting function becomes valid when all the conditions listed 
#

$ The safety output 2 is ON.
$ The incandescent lamp with 3.6 to 30W shall be connected to 

either muting lamp output 1 or 2, or to both of the inputs.

$ The output of the muting sensors S3 and S4 shall be changed 

from OFF (open) to ON. At this time, the time difference occurred 
by changing the output of the muting sensors S3 and S4 into ON 
status shall be 0 to 3 sec.

 

Muting sensor input
&9!*!"!JQV25Z['

This is used to connect the muting sensor. For following devices, 
photoelectric sensor with semiconductor output, inductive proxim-
ity sensor, position switch on NO (Normally Open) contacting point, 
etc. are available for applying to the muting sensor.     
> ;>‚>>*6>* ?^?*
[ ;[‚[[*6>* ^?^*

 

Muting lamp

This lamp is used to show that the product is in muting state. Two 
lamps can be connected. Even if one of the two lamps breaks, the 
muting operation can be continued because of another lamp. The 
broken lamp can be replaced without suspending your work.

Summary of Contents for SF-C14EX-01

Page 1: ...ol system started to function with this timing Wiring Be sure to carry out the wiring in the power supply OFF condition All electrical wiring should conform to the regional electrical regulations and laws The wiring should be done by engineer s having special electrical knowledge them in the same raceway This can cause malfunction due to induction WARNING Maintenance The periodical inspection of t...

Page 2: ...put 1 Muting output T2 AUX2 Auxiliary output 2 Override output O1 Override input terminal Valid AUX3 Auxiliary output 3 Blown lamp output O2 AUX4 Auxiliary output 4 Light curtain auxiliary output L1 Muting lamp output 1 IE Interference prevention terminal Emission L1 IE Interference prevention terminal Emission L2 Muting lamp output 2 IR Interference prevention terminal Receipt L2 IR Interference ...

Page 3: ...c 6 used as a muting sensor wire it as shown in S3 S3 S4 S4 S4 S3 R terminals S11 to S12 and S21 to S22 directly tractors 10 9 5 5 The diagram shows operation with safety outputs 1 2 in manual reset mode Light received Light blocked Light curtain Invalid Valid Emergency stop ON OFF Muting sensor 1 ON OFF ON OFF Reset input 1 ON OFF Reset input 2 ON OFF Reset input 3 ON OFF Safety output 1 14 and 2...

Page 4: ...output 2 is not turned OFF Safety output 1 This is the output corresponding to light curtain in light received light blocked status However if the emergency stop is valid safety output 1 is OFF H This is the output corresponding to the light curtain in light received light blocked status including the muting state However if the emergency stop is valid the safety output 2 is OFF Safety output 3 Th...

Page 5: ...ble 2 The interference prevention wire for connection with a unit of light curtain should be 12 core cable 3 Refer to the instruction manual enclosed with the light curtain for details of the connection with a unit of light curtain 5 2 _ 9 5 2 9 5 5 5 When using this product as a safety equipment for a press machine in Japan this product s installation electrical wiring inspection and supervisor w...

Page 6: ...mergency stop input R 0 RX Safety output Note 1 Safety output 1 Safety output 2 Safety output 3 PNP NPN open collector transistor 3 J 5 7 RXX between the safety output and V R RXX 6 R Including power supply OFF condition 7 X RR No load to maximum output current J 5 5 7 RXX between the safety output and 0V R RXX 6 R Including power supply OFF condition 7 X RR No load to maximum output current Opera...

Page 7: ...d Input voltage monitor error Check the supply voltage and the voltage capacity blinks on the digital indicator red Safety output error Safety output short circuited Wire the safety output wire cor rectly lights up on the digital indicator red Light curtain commu nication error Check if the light curtain is con nected correctly Check the operation of the con nected light curtain blinks on the digi...

Page 8: ... ZZ Z Z Z 2 2 2431 1 Ushiyama cho Kasugai shi Aichi 486 0901 Japan Y Y Y _ About our sale network please visit our website 0 RX ...