Refrigerant charging
Addition amount of refrigerant [
g
/m]
Tube diameter
Main tube
Branch tube
L
La, Lb
La, Lb, Lc
Lc, Ld, Le, Lf
U-200PZH2E8
TWIN
Liquid tube : ø 9.52
Gas tube : ø 25.4
60
45
-
-
TRIPLE
60
-
45
-
DOUBLE TWIN
60
45
-
20
U-250PZH2E8
TWIN
Liquid tube : ø 12.7
Gas tube : ø 25.4
80
45
-
-
DOUBLE TWIN
80
45
-
45
Make additional charges by adding up tube length in an order of main tube (L) branch tube (La Lb Lc wide diameter) and then selecting the amount of
refrigerant corresponding to the remaining (after 30m for the twin connection and after 20m for the triple/double-twin connections) liquid tube diameter and
tube length from the table above.
Wiring
Power supply
(220-230-240V~)
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Control
cable
Control
cable
Control
cable
Control
cable
protective
earth
protective
earth
(TRIPLE type)
protective
earth
protective
earth
Circuit breaker
Switch
protective earth
: functional earthing
(for the shielded cable)
(DOUBLE TWIN type)
Power supply
(220-230-240V~)
Power supply
(220-230-240V~)
Power supply
(220-230-240V~)
Power supply
(380-400-415V 3N~)
SM830276-00_欧州向け R32シングル TD&SM.indb 16
2019/02/27 11:54:30
Summary of Contents for S-50PU2E5B
Page 12: ... MEMO Xi SM830276 00_欧州向け R32シングル TD SM indb 12 19 02 26 15 26 22 ...
Page 160: ...1 14 8 MEMO SM830276 00_欧州向け R32シングル TD SM indb 8 2019 02 27 11 55 39 ...
Page 176: ... MEMO 2 16 SM830276 00_欧州向け R32シングル TD SM indb 16 19 02 28 13 23 00 ...
Page 182: ... MEMO 3 6 SM830276 00_欧州向け R32シングル TD SM indb 6 19 02 26 10 39 17 ...
Page 238: ... MEMO 5 38 SM830276 00_欧州向け R32シングル TD SM indb 38 19 02 28 13 29 52 ...
Page 316: ...201903 SM830276 00_欧州向け R32シングル TD SM indb 1 19 02 15 8 52 12 ...