8
8
Control of 2WAY SYSTEM
2. Wireless Remote Controller
2. Installing the Receiver
1
Remove the bottom case.
Attention
Mounting the bottom case
Tighten the screws securely until the screw
heads touch the bottom case.
(Otherwise, loose screw heads may hit the
PCB and cause malfunction when mounting
the top case.)
Do not over-tighten the screws.
(The bottom case may be deformed, resulting
in fall of the unit.)
Connecting the remote controller wiring
Arrange the wires as shown in the illustration for in step 2
,
avoiding unnecessary wires being stored in the case. (Caught
wires may destroy the PCB.)
Avoid wires touching parts on the PCB.
(Caught wires may destroy the PCB.)
Flat-blade
screwdriver
Bottom
case
Insert the driver
and slightly turn.
2
Mount to the wall.
e
p
y
t
d
e
d
d
e
b
m
E
e
p
y
t
d
e
s
o
p
x
E
Preparation: Make 2 holes for screws using a driver.
Preparation: Make 2 holes for screws using a driver.
1
3
2
Cut here with a
nipper and remove
the burr with
.e
l if
a
Mount the top case.
Align the claws of
the top case and
then align the claws
of the bottom case.
Mount the bottom case
to the wall.
Connect the remote controller wiring.
Arrange the wires along the groove of the case.
Wood screw (supplied)
Claw
Hole for screw
e
h
t
x
if
o
t
ll
a
W
receiver
Claw (2 places)
Top case
(Back side)
Remove the coating. Approx. 6 mm
Remove the sheath. Approx. 150 mm
Make sure the wiring connection
is in the correct direction.
Clamper
(supplied)
Pass through
the hole.
Bottom case (Back side)
1
3
2
Avoid the wire
being caught.
Mount the top case.
Align the claws of
the top case and
then align the claws
of the bottom case.
Mount the bottom case to
the wall.
Pass the wire through the hole
in the centre of the bottom case.
Connect the remote controller wiring.
Wood screw (supplied)
Claw (2 places)
Claw
Hole for screw
Terminal board
Bottom case (Back side)
Remove the coating.
Approx. 6 mm
Make sure the wiring connection
is in the correct direction.
Top case
(Back side)
2
Control of 2WAY SYSTEM
2. Wireless Remote Controller
3. Wiring the Receiver
Specifications
Wiring for the receiver
Wiring diagram
Type of wiring
Use cables of 0.5 to 1.25 mm
2
.
Total wire length:
400 m or less
(The wire length between indoor
units should be 200 m or less.)
Number of connectable units
Remote controller and receiver: Max. 2, Indoor unit: Max. 8
Attention
R1 R2
R1 R2
R1 R2
1 2
1 2
1 2
Wired RC
Receiver
ti
n
u
r
o
o
d
n
I
ti
n
u
r
o
o
d
n
I
ti
n
u
r
o
o
d
n
I
RC wiring
Receiver
*Wiring as shown below is prohibited.
1
2
R1
R2
Indoor unit
Terminals for RC wiring
Receiver
RC wiring (fi eld supply)
•
No polarity
Model No.
CZ-RWSC3, CZ-RWRC3
Dimensions
(H) 120 mm × (W) 70 mm × (D) 20 mm
Weight
75
Temperature/Humidity range
0 °C to 40 °C / 20 % to 80 % (No condensation)
*Indoor use only.
Power Source
DC16 V (supplied from indoor unit)
Installation when setting Main/Sub for the remote controller and the receiver
After installation, according to the "Main/Sub setting" in the "Setting" section, set one to [Main] and the other to [Sub].
Setting the wired remote controller to [Main] is recommended.
The remote controller and the receiver can be connected to any indoor unit for operation.
Note
1 2
1 2
R1 R2
R1 R2
R1 R2
R1 R2
RC wiring (fi eld supply)
•
No polarity
Indoor unit
Indoor unit
Indoor unit
Indoor unit
1 2
1 2
R1 R2
Terminals for
RC wiring
)
b
u
S
(
r
e
v
i
e
c
e
R
)
b
u
S
(
r
e
v
i
e
c
e
R
Wired RC (Main)
Wired RC (Main)
Indoor unit
Using 1 indoor unit
Using more than 1 indoor unit
RC wiring
)
y
l
p
p
u
s
d
l
e
if
(
•
No polarity
Installation
example
Be careful not to connect cables to other terminals of indoor units (e.g. power source wiring
terminal). Malfunction may occur.
Do not bundle together with the power source wiring or store in the same metal tube. Operation
error may occur.
If noise is induced to the unit power supply, attach a noise filter.
For the RC wiring of field supply, please use insulated wires with sheath.
The insulation thickness should be at least 1 mm.
Regulations on wire diameters differ from locality to locality. For field wiring
rules, please refer to your LOCAL ELECTRICAL CODES before beginning.
You must ensure that installation complies with all relevant rules and regulations.
8-33
SM830276-00_欧州向け R32シングル TD&SM.indb 33
19/02/18 11:16:11
Summary of Contents for S-50PU2E5B
Page 12: ... MEMO Xi SM830276 00_欧州向け R32シングル TD SM indb 12 19 02 26 15 26 22 ...
Page 160: ...1 14 8 MEMO SM830276 00_欧州向け R32シングル TD SM indb 8 2019 02 27 11 55 39 ...
Page 176: ... MEMO 2 16 SM830276 00_欧州向け R32シングル TD SM indb 16 19 02 28 13 23 00 ...
Page 182: ... MEMO 3 6 SM830276 00_欧州向け R32シングル TD SM indb 6 19 02 26 10 39 17 ...
Page 238: ... MEMO 5 38 SM830276 00_欧州向け R32シングル TD SM indb 38 19 02 28 13 29 52 ...
Page 316: ...201903 SM830276 00_欧州向け R32シングル TD SM indb 1 19 02 15 8 52 12 ...