1-11-4
1
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
Outdoor unit
Outdoor unit
Outdoor unit
: Branch point
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
More than 2m required
Central Controller
(5) Use shielded wires for inter-unit control wiring (C) and ground the
shield on both sides, otherwise misoperation from noise may occur.
Connect wiring as sh
on page 1-11-2.
own in Section “
Wiring System Diagrams”
(6) •
Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 5 or 3 *1.5 mm
2
flexible cord. Type designation 60245 IEC57 (H05RN-F, GP85PCP etc.) or heavier cord.
•
Use the standard power supply cables for Europe (such as H05RN-F or H07RN-F which conform to CENELEC (HAR)
rating specifications) or use the cables based on IEC standard. (60245 IEC57, 60245 IEC66)
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also occur. Therefore,
ensure that all wiring is tightly connected.
When connecting each power wire to the terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the
wire securely with the terminal screw.
(Functional earthing)
(Functional earthing)
Shielded wire
Stranded wire
Ring
pressure
terminal
Screw and
Special washer
Ring
pressure
terminal
Terminal board
Ring pressure
terminal
Screw
Special
washer
Wire
Wire
Strip 10 mm
How to connect wiring to the terminal
For stranded wiring
(1) Cut the wire end with cutting pliers, then strip the insulation
to expose the stranded wiring about 10 mm and tightly
twist the wire ends.
(2) Using a Phillips head screwdriver, remove the terminal
screw(s) on the terminal board.
(3) Using a ring connector fastener or pliers, securely clamp
each stripped wire end with a ring pressure terminal.
(4) Place the ring pressure terminal, and replace and tighten
the removed terminal screw using a screwdriver.
(3) Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting.
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
NO
Branch point
<Type U2>
SM830276-00_欧州向け R32シングル TD&SM.indb 4
2019/02/27 11:54:22
Summary of Contents for S-50PU2E5B
Page 12: ... MEMO Xi SM830276 00_欧州向け R32シングル TD SM indb 12 19 02 26 15 26 22 ...
Page 160: ...1 14 8 MEMO SM830276 00_欧州向け R32シングル TD SM indb 8 2019 02 27 11 55 39 ...
Page 176: ... MEMO 2 16 SM830276 00_欧州向け R32シングル TD SM indb 16 19 02 28 13 23 00 ...
Page 182: ... MEMO 3 6 SM830276 00_欧州向け R32シングル TD SM indb 6 19 02 26 10 39 17 ...
Page 238: ... MEMO 5 38 SM830276 00_欧州向け R32シングル TD SM indb 38 19 02 28 13 29 52 ...
Page 316: ...201903 SM830276 00_欧州向け R32シングル TD SM indb 1 19 02 15 8 52 12 ...