7
7
When the operating mode at the priority remote controller is changed, the operating modes of other remote
controllers change as shown below.
Mode change at priority remote controller Operating modes at other remote controllers
Current mode
New mode
Current mode
New mode
Cooling or dry
Heating
Cooling or dry
Heating
Fan
Fan (not changed)
Heating
Cooling
Heating
Cooling
Fan
Fan (not changed)
Cooling
Dry
Cooling
Cooling (not changed)
Dry
Dry (not changed)
Heating
Dry
Heating
Cooling
Fan
Fan (not changed)
Cooling or dry
Fan
Cooling
Cooling (not changed)
Dry
Dry (not changed)
Fan
Fan (not changed)
Heating
Fan
Heating
Heating (not changed)
Fan
Fan (not changed)
Item code
Item
Description
05
Fan speed setting when
heating thermostat is OFF
Changes the fan speed setting when the heating thermostat is OFF.
06
Heating intake
temperature shift
Shifts the intake temperature during heating.
Can be set when the body thermostat is used.
07
Electric heater installation
Set when cost distribution is performed using an AMY central control
system or similar system, and when an optional electric heater is installed.
(This is unrelated to control of the electric heater.)
08
Humidifying when heater
thermostat is OFF
Normally humidifying does not occur when the thermostat is OFF during
heating operation. However, this setting can be changed in order to
increase the amount of humidifying.
Caution: In order to avoid water leakage and damage to the fan, do not use
this setting unless a vaporizing humidifier is used.
0D
Permit/prohibit automatic
heating/cooling
This setting can be used to prevent the automatic heating/cooling display
on the remote controller if the unit configuration permits automatic heating/
cooling operation.
0F
Cooling-only
This setting allows a heat pump indoor unit to be operated as a cooling-
only unit.
NOTE
•
In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFF
unless a vaporizing humidifier is used.
•
Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.
•
Do not change any setting data that does not appear in this list.
7-12
SM830276-00_欧州向け R32シングル TD&SM.indb 12
19/02/28 13:33:39
Summary of Contents for S-50PU2E5B
Page 12: ... MEMO Xi SM830276 00_欧州向け R32シングル TD SM indb 12 19 02 26 15 26 22 ...
Page 160: ...1 14 8 MEMO SM830276 00_欧州向け R32シングル TD SM indb 8 2019 02 27 11 55 39 ...
Page 176: ... MEMO 2 16 SM830276 00_欧州向け R32シングル TD SM indb 16 19 02 28 13 23 00 ...
Page 182: ... MEMO 3 6 SM830276 00_欧州向け R32シングル TD SM indb 6 19 02 26 10 39 17 ...
Page 238: ... MEMO 5 38 SM830276 00_欧州向け R32シングル TD SM indb 38 19 02 28 13 29 52 ...
Page 316: ...201903 SM830276 00_欧州向け R32シングル TD SM indb 1 19 02 15 8 52 12 ...