background image

20

 

CAUTION

(1)  When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units 

except any one of the outdoor units. 

 

 (When shipping: In shorted condition.) 

 

For a system without link (no wiring connection between outdoor units), do not remove the short plug.

(2)  Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 4-3) 

Outdoor unit

Outdoor unit

Outdoor unit

Prohibited

Prohibited

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Fig. 4-3

(3)

 

Do not install inter-unit control wiring such as star branch wiring. Star branch wiring causes mis-address setting. (Fig. 4-4)

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

Branch point

NO

NO

Fig. 4-4

(4)

   

If branching the inter-unit control wiring, the number of branch points should be 16 or fewer. 

 

(Branches that are less than 1 m are not included in the total branch number.) (Fig. 4-5)

Indoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

more than 1 m

less than 1 m

16 or fewer

Branch 
Point

more than 1 m

Fig. 4-5

(5)  Use shielded wires for inter-unit control wiring (c) and 

ground the shield on both sides, otherwise misoperation 
from noise may occur. (Fig. 4-6) 
Connect wiring as shown in Section “4-3. Wiring System 
Diagrams”.

 

WARNING

Loose wiring may cause the terminal to overheat or result 

in unit malfunction. A fire hazard may also occur. Therefore, 

ensure that all wiring is tightly connected.

Shielded wire

Ground

Ground

When connecting each power wire to the terminal, follow the 
instructions on “How to connect wiring to the terminal” and fasten 
the wire securely with the terminal screw.

Fig. 4-6

(6)

   

Use the standard power supply cables for Europe (such as 
H05RN-F or H07RN-F which conform to CENELEC (HAR) 
rating speci

fi

 cations) or use the cables based on IEC 

standard. (245 IEC57, 245 IEC66)

P07-T11630.indb   20

P07-T11630.indb   20

2/27/2012   9:21:20 AM

2/27/2012   9:21:20 AM

Summary of Contents for S-100PN1E5A

Page 1: ......

Page 2: ... responsible for improper installation or maintenance service including failure to follow the instructions in this document At least 2 5 m Indoor unit of this room air conditioner shall be installed in a height of at least 2 5 m SPECIAL PRECAUTIONS WARNING When Wiring In laundry rooms Do not install in laundry rooms Indoor unit is not drip proof ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR...

Page 3: ...num fins of the outdoor unit You may get injured Ventilate any enclosed areas when installing or testing the refrigeration system Escaped refrigerant gas on contact with fire or heat can produce dangerously toxic gas Confirm after installation that no refrigerant gas is leaking If the gas comes in contact with a burning stove gas water heater electric room heater or other heat source it can cause ...

Page 4: ... 2 Suspending the Indoor Unit 3 3 Installing the Drain Pipe 3 4 Connecting Duct to Indoor Unit 3 5 External Static Pressure Setting for Dc Fan Motor Model 3 6 External Static Pressure Setting for AC Fan Motor Model 4 ELECTRICAL WIRING 18 4 1 General Precautions on Wiring 4 2 Recommended Wire Length and Wire Diameter for Power Supply System 4 3 Wiring System Diagrams 5 HOW TO PROCESS TUBING 22 5 1 ...

Page 5: ...lyethylene insulation for copper tubes as required to precise length of tubing Wall thickness of the insulation should be not less than 8 mm 3 Use insulated copper wire for field wiring Wire size varies with the total length of wiring Refer to 4 ELECTRICAL WIRING for details CAUTION Check local electrical codes and regulations before obtaining wire Also check any specified instructions or limitati...

Page 6: ... an appropriate position from which every corner of the room can be uniformly cooled select a location where the ceiling is strong enough to support the weight of the unit select a location where tubing and drain pipe have the shortest run to the outdoor unit allow room for operation and maintenance as well as unrestricted air flow around the unit install the unit within the maximum elevation diff...

Page 7: ... height from the floor to ceiling exceeds three meters air flow distribution deteriorates and the effect is decreased Fig 3 1 POSITION OF SUPENSION BOLT Apply a joint canvas between the unit and duct to absorb unnecessary vibration Install the unit leaning to a drainage hole side as a figure for easy water drainage Top view Unit mm Inspection hole Control box 600 x 600 600 Front 1000 600 Front vie...

Page 8: ...n 2 5 4 r e g g n a H 6 1 x o b l o r t n o C A i r F l o w A i r F l o w D r a i n p i p e c o n n e c t i o n U N I T m m Outside Dimensions MODEL NO S 36PN1E5A S 45PN1E5A S 50PN1E5A 20 45 65 65 55 55 100 840 670 900 250 80 780 740 523 24 ø4 5 22 ø4 5 650 30 30 134 23 32 58 48 48 65 31 31 187 161 64 650 P65 x 10 585 P65 x 9 P07 T11630 indb 8 2 27 2012 9 20 57 AM ...

Page 9: ... Female screw PT1 4 Dutch connection 2 5 Hangger 4 6 Control box 1 D r a i n p i p e c o n n e c t i o n A i r F l o w A i r F l o w U N I T m m Outside Dimensions MODEL NO S 60PN1E5A S 71PN1E5A 845 P65 x 13 57 5 960 523 64 20 65 28 ø4 5 30 ø4 5 1000 1060 890 55 23 134 55 65 100 250 80 780 P65 x 12 1120 650 30 30 134 23 32 58 48 48 65 31 31 187 161 P07 T11630 indb 9 2 27 2012 9 21 04 AM ...

Page 10: ...pe connection gas 1 O D ø15 88 Flared 2 Pipe connection liquid 1 O D ø9 52 Flared 3 Drain pipe connection 2 Female screw PT1 4 Dutch connection 2 4 r e g g n a H 5 1 x o b l o r t n o C 6 1320 250 80 1200 1260 1160 1090 65 65 20 60 100 57 5 1040 P65 x 16 975 P65 x 15 44 ø4 5 46 ø4 5 523 64 650 30 30 32 58 48 48 65 31 31 187 161 P07 T11630 indb 10 2 27 2012 9 21 10 AM ...

Page 11: ...ig 3 3 Cut the ceiling material if necessary 3 Thread the 3 hexagonal nuts and 2 washers field supply onto each of the 4 suspension bolts Figs 3 5 and 3 6 Use 1 nut and 1 washer for the upper part and 2 nuts and 1 washer for the lower part so that the unit will not fall off the suspension lugs 3 2 Suspending the Indoor Unit Depending on the ceiling type Insert suspension bolts Fig 3 3 or Use exist...

Page 12: ...ng on the unit side when connecting the drain pipe The pipe should not be allowed to hang unsupported from its connection to the unit Fasten the pipe to a wall frame or other support as close to the unit as possible Fig 3 13 Support pieces Fig 3 8 2 After connecting the drain pipe securely wrap the supplied packing and drain pipe insulator around the pipe then secure it with the vinyl clamps Fig 3...

Page 13: ...ontroller Air outlet volume is automatically adjusted to the rated airflow volume with the auto airflow control drive Flow of External Static Pressure Start external static pressure setting Finish the ducting and electrical wiring and prepare it for use Note 1 External static pressure should be set during initial operations after installation before the cooling and heating test run When operating ...

Page 14: ...r water leakages Refer to Fig 3 18 for the external static pressure setting range There are cases in which automatic variable dampers and other mounted items may trigger the P12 alarm on systems that modify the static pressure of outdoor units when the auto airflow volume control operations or setting check operations are carried out if high static pressure in the outdoor unit is lowered In this e...

Page 15: ...nated 6 Press the button The fan motor will stop operating and the LCD display will return to the normal stop mode 3 5 2 2 Auto Airflow Volume Control Operations and External Static Pressure Setting Check Operation 1 Press and hold down the button for 4 or more seconds will be displayed on the remote controller s LCD display 2 Press the button to commence the test run Test Run will be displayed on...

Page 16: ...ling Heating Cooling Heating Cooling Heating Setting at shipment Tap Item code S 60PN1E5 S 71PN1E5 P Q diagram S 125PN1E5 P Q diagram S 140PN1E5 S 100PN1E5 P Q diagram External Static Pressure Pa External Static Pressure Pa Air Volume m3 min External Static Pressure Pa External Static Pressure Pa Air Volume m3 min Air Volume m3 min Air Volume m3 min Limit line Limit line Limit line Limit line P Q ...

Page 17: ...e as is at shipment For high static pressure duct switch Fan Motor connector to plug in boost tap white connector to elevate air volume 0 10 20 30 40 50 60 70 80 8 1 8 0 10 20 30 40 50 60 70 80 0 2 0 1 P Q CURVE external Static Pressure Pa Air Volume m3 min Lo S 36PN1E5 P Q CURVE S 45PN1E5 S 50PN1E5 Me standard tap Hi boost tap SHi Lo Me standard tap Hi boost tap SHi external Static Pressure Pa Ai...

Page 18: ...ase refer to your LOCAL ELECTRICAL CODES before beginning You must ensure that installation complies with all relevant rules and regulations 8 To prevent malfunction of the air conditioner caused by electrical noise care must be taken when wiring as follows The remote control wiring and the inter unit control wiring should be wired apart from the inter unit power wiring Use shielded wires for inte...

Page 19: ... supplied with the remote controller unit Optional Auto address setting can be executed by remote controller automatically Refer to the installation instructions supplied with the remote controller unit optional Fig 4 2 Power supply Indoor unit Ground Ground Ground Remote controller Remote controller Ground No 1 Indoor unit No 1 Power supply 220 230 240V 50Hz 220 230 240V 50Hz 3 phase model connec...

Page 20: ...number Fig 4 5 Indoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Outdoor unit Outdoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit Indoor unit more than 1 m less than 1 m 16 or fewer Branch Point more than 1 m Fig 4 5 5 Use shielded wires for inter unit control wiring c and ground the shield on both sides otherwise misoperation from noise may occur Fig 4 6 Connect wi...

Reviews: