12
3-3. Installing the Drain Pipe
Drainage hole
Thermal insulator
(Accessories)
Hose clip
(Accessories)
(1) Prepare standard hard PVC pipe (O.D. 32 mm) for the drain
and use the supplied hose band to prevent water leaks.
The PVC pipe must be purchased separately.
CAUTION
Fig.3-11
Do not install the pipe with an upward gradient from the
connection port. This will cause the drain water to fl ow
backward and leak when the unit is not operating.
(Fig. 3-12)
Do not use adhesive tape at the drain connection port on
the indoor unit
Insert the drain pipe until it contacts the socket, and then
secure it tightly with the hose band.
Prohibited
Upward gradient
Do not use the supplied drain hose bent at a 90° angle.
(The maximum permissible bend is 45°.)
Tighten the hose clamps so their locking nuts face
upward. (Fig. 3-8)
Hose clip (Accessory)
Heat insulator (Local supply)
(The thickness must be at
least 8 mm.)
Flexible hose with
heat insulator
(Accessory)
PVC pipe
(O.D. ø32)
(Local supply)
It may be required to take off this part for checking
or servicing the drain up motor. Please do not glue.
To be glued
Make sure that there is no clearance here.
Fig.3-12
Do not apply force to the piping on the unit side when
connecting the drain pipe. The pipe should not be allowed to
hang unsupported from its connection to the unit. Fasten the
pipe to a wall, frame, or other support as close to the unit as
possible. (Fig. 3-13)
Support pieces
Fig.3-8
(2) After connecting the drain pipe securely, wrap the supplied
packing and drain pipe insulator around the pipe, then secure it
with the vinyl clamps . (Fig. 3-9)
Fig.3-13
Drain insulator (supplied)
Vinyl clamps
(field supply)
Fig.3-9
3-4. Connecting Duct to indoor Unit
(1) Install the duct (local supply) for the Dimension of the
installation hole.
Use M5 self-tapp Screws for installation see the Figure 3-2.
(2) The duct connection of the air outlet needs thermal insulation.
Thermal insulator
(Local arrangement)
Air outlet
NOTE
Make sure the drain pipe has a downward gradient (1/100 or more)
and that there are no water traps.
CAUTION
Fig.3-14
•
Do not install an air bleeder as this may cause water to
spray from the drain pipe outlet. (Fig. 3-10)
NOTE
•
Select an air-intake grille with a filter at a local shop.
Air bleeder
Prohibited
•
To get clean air and to extend the service life of the air
conditioner, an air filter must be installed in the air intake. For
installation and cleaning the air filter, consult your dealer or
service center.
Fig.3-10
P07-T11630.indb 12
P07-T11630.indb 12
2/27/2012 9:21:17 AM
2/27/2012 9:21:17 AM