EN - 35
EN - 34
Setting and Indication
Mode
DIP
switch
SW13-8
DIP
switch
SW13-7
Rotary switch
(Knob) position
Display/Setup
Remarks
Back mode 2
OFF
ON
ON
High pressure/
Intermediate pressure/
Unit outlet pressure/
Low pressure display
High pressure: *** H (MPa)
Intermediate pressure: *** c (MPa)
Unit outlet pressure: *** o (MPa)
Low pressure: *** (MPa)
▲ pressing: Increase the displayed value
▼ pressing: Reduce the displayed value
OFF
Other temperature display
(Suction, Unit outlet, Split cycle outlet,
Gas cooler outlet)
**** (°C)
OPERATION
MODE
Oil level display
Displays by “Lower limit”/
“Intermediate”/“Upper limit”
For details, refer to “
Oil Level Control
Method
.”
STANDARD
SETTING
Electronic expansion valve opening
display (Oil control)
MOV1: 1. *** (step)
- - -
: 2. 0 (fixed)
For detail, refer to “
Oil Level Control
Method
.”
▲ pressing: Increase the displayed value
▼ pressing: Reduce the displayed value
PRESSURE
Electronic expansion valve opening
display
(Pressure reduction, Gas return,
Liquid return)
MOV5: 5. *** (step)
MOV6: 6. *** (step)
MOV7: 7. *** (step)
―
FREQ
(FREQUENCY) Compressor current
**** (A)
―
SUC
(SUCTION)
Gas cooler fan speed
**** (rpm)
―
DIS
(DISCHARGE)
―
―
▲ pressing: Software Version
▼ pressing: Erase Alarm history
ALM HISTORY Ambient temperature
**** (°C)
―
Low Pressure Control Method
Compressor capacity is controlled by changing the inverter frequency based on the difference between the low
pressure and set value by adjusting the low pressure to the set value (ON value to OFF value).
However, compressor operation continues even if the low pressure becomes below “OFF value” and finally stops
when the low pressure reaches below the “Lim value”.
* Lim value = OFF value - Diff value
For the setting of Diff value, refer to “Low Pressure Setting” of “Setting and Indication”.
Short Cycle Prevention Control
After the compressor has been stopped, and even the pressure becomes higher than the “ON value“, stopping
continues for the forced stopping time (30 to 180 sec).
Control Functions
01_OCU-CR1000VF8A.indd 34
2019/08/27 10:56:08