background image

FP-e Series

Technical data

 General specifications

Item

Rated voltage

Operating voltage range

Allowed momentary power off time

Ambient temperature

Storage temperature

Ambient humidity

Storage humidity

Breakdown voltage

Insulation resistance

Description

24 V DC

21.6 to 26.4 V DC

10 ms

0 to +55°C

–20 to +70°C

30 to 85%RH (non-condensing)

30 to 85%RH (non-condensing)

Vibration resistance

10 to 55 Hz, 1 cycle/min.
Double amplitude: 0.75 mm, 10 min. on X, Y, and Z axes

Shock resistance

Noise resistance

Operating condition

Current consumption

Protection

Mass

98 m/s

2

 or more, 4 times on X, Y, and Z axes

1000V (p-p) with pulse widths 50 ns and 1 µs (based on in-house measurements)

Free from corrosive gases and excessive dust

200 mA or less (24 V DC)

IP66-compliant front section (Only when a rubber packing is used.)

Approx. 130 g

Input terminals (COM, X0 to Xn)
Output terminals (Y0 to Y4)

Power supply terminal, Function earth
Input terminal (A0, A1)
COM. (RS232C) terminal

500 V AC for 1 minute

 DC input specifications (X0 to X7)

Item

Number of input

Insulation method

Rated input voltage

Operating voltage range

Rated input current

Description

8 points (6 points for thermocouple input type)

Optical coupler

24 V DC

21.6 to 26.4 V DC

Approx. 4.3 mA

Input points 
per common

8 points/common (6 points/common for 
thermocouple input type) 
Either the positive or negative of the input power 
supply can be connected to common terminal.

ON voltage/ON current

OFF voltage/OFF current

19.2 V or less/4 mA or less

2.4 V or more/1 mA or more

Input impedance

Approx. 5.1 k  (X0, X1)
Approx. 5.6 k  (X2 to X7)

Response 
time

Operating mode indicator

OFF to ON

ON to OFF

50 µs or less (X0, X1) 

Note 1)

100 µs or less (X2 to X5) 

Note 1)

2 ms or less  (X6, X7)

50 µs or less (X0, X1) 

Note 1)

100 µs or less (X2 to X5) 

Note 1)

2 ms or less  (X6, X7)

LCD display (I/O monitor mode)

 Thermocouple input specifications

Item

Number of input

Temperature sensor type

Input range

Accuracy

Resolution

Conversion time

Description

2 points (CH0: WX1, CH1: WX2)

Thermocouple type K

–30.0 to 300.0°C 

1)

 (

–22 to 572°F

)

±0.5%FS±1.5°C (FS = –30 to 300°C)

0.1°C

250 ms/2CH 

2)

Insulation method

Between internal circuit and thermocouple input 
circuit: noninsulated 

3)

Between CH0 and CH1 of thermocouple input: 
PhotoMOS insulation

Detection function of 
wire disconnection

Available

Output terminal (Y5)

Power supply terminal, Function earth
Input terminal (COM, X0 to Xn, A0, A1)
COM. (RS232C) terminal

1500 V AC for 1 minute

Input terminals (COM, X0 to Xn)

Output terminals (Y0 to Y4)

500 V AC for 1 minute

Input terminals (COM, X0 to Xn)

Output terminals  (Y0 to Y5)

Input terminals (COM, X0 to Xn)
Output terminals (Y0 to Y5)

Power supply terminal, Function earth
Input terminal (A0, A1)
COM. (RS232C) terminal

Min. 100 M  
(measured with 500 V DC)

Note 1) 

X0 through X5 are inputs for the high-speed counter and have a fast response 

  

time. If used as normal inputs, you should insert a timer in the program as 

 

chattering and noise may be interpreted as an input signal.  

 

Also, the above specifications apply when the rated input voltage is 24V DC 

 

and the temperature is 25°C.

1)

 Temperature can be measured up to 330°C (

626°F

). When the measured temperature 

exceeds 330°C (

626°F

) or the thermocouple wiring is disconnected, “K20000” is written 

to the register.

2)

 Temperature conversion for thermocouple input is performed every 250 ms. The 

conversion data is updated on the internal data register after the scan is completed.

3)

 The internal circuit and thermocouple input circuit are not insulated. Therefore, use the 

nongrounding type thermocouples and sheath tubes.

Clearwater Tech - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.clrwtr.com - Email: [email protected]

Summary of Contents for Network Adaptor

Page 1: ...Matsushita Programmable Controller FP e 48 mm Clearwater Tech Phone 800 894 0412 Fax 208 368 0415 Web www clrwtr com Email info clrwtr com ...

Page 2: ... well as timer counter settings and elapsed values can also be displayed Built in operation switch Setting values can be changed The operation switch can also be used as an input Panel mounted type in accordance with IP66 IEC standard To match panel design a black faceplate is available Matches FP0 intelligence equivalent to FP0 C14 Compact Panel mountable little space is taken up on the control p...

Page 3: ...ut Feeder roller Lead wire and tape Cutter Encoder Motor START STOP signal Inverter Cutter blade control signal Input encoder output into the high speed counter Equipped with RS485 and RS232C interfaces Two point K type thermocouple 30 to 300 C connection is possible equipped with thermocouple input Can be used in place of a temperature controller or used to control them PID instruction function H...

Page 4: ...PROG MODE 1 2 SET 5 4 3 2 1 0 FP e I PROG MODE 1 2 SET 5 4 3 2 1 0 FP e PV R PROG MODE 1 2 SET 5 4 3 2 1 0 FP e Features 1 5 character 2 line 3 color Display Simple characters and numerical values can be displayed Simple error messages as well as operation instructions and timer counter set values can be displayed 2 Front Operation Switch Timer Counter set values can be changed using front operati...

Page 5: ...n no power is supplied at all Not available Not available 6 points in total X0 and X1 50 µs X2 to X5 100 µs Programming method Control method Number of controllable I O points Program memory Program capacity Number of instruction Operation speed I O update and Base time Internal relay R Special internal relay R Timer Counter T C Data register DT Special data register DT Index registers IX IY Diffe...

Page 6: ... µs or less X0 X1 Note 1 100 µs or less X2 to X5 Note 1 2 ms or less X6 X7 LCD display I O monitor mode Thermocouple input specifications Item Number of input Temperature sensor type Input range Accuracy Resolution Conversion time Description 2 points CH0 WX1 CH1 WX2 Thermocouple type K 30 0 to 300 0 C 1 22 to 572 F 0 5 FS 1 5 C FS 30 to 300 C 0 1 C 250 ms 2CH 2 Insulation method Between internal ...

Page 7: ...rmat Stop bit 1 bit 2 bit Parity Not available Available Odd number Even number Data length 7 bit 8 bit Beginning code STX available STX not available Ending code CR CR LF not available ETX Communication mode General purpose communication Computer link 99 5 6 Data output order No of connected units Starting from 0 bits per character Relay output specifications Y5 Item Output type Rated control cap...

Page 8: ...ebell Dublin 12 Republic of Ireland Tel 01 4600969 Fax 01 4601131 www matsushita ie Italy Matsushita Electric Works Italia s r l Via del Commercio 3 5 Z I Ferlina I 37012 Bussolengo VR Tel 045 6752711 Fax 045 6700444 www matsushita it Portugal Matsushita Electric Works España S A Portuguese Branch Office Avda 25 de Abril Edificio Alvorada 5 ºE 2750 512 Cascais Portugal Tel 21 4828266 Fax 21 482742...

Reviews: