KW2G/ KW2G-H Eco-POWER METER
38
+
+
+
+
Current alarm setting mode
*It is only when ‘AL-C’ is selected on unit for pulse output setting mode.
Mode defines the ratio of current used for alarm output. (Ratio for the rated current)
・
It is set the range of 0.1 to 100.0%.
Set it using <ITEM/
△
>,<SET>+<ITEM/
△
>.
(0.1 to 100.0)
Increase
Decrease
↓
<SET>
Stand-by alarm setting mode 1
*It is only when ‘AL-S’ is selected on unit for pulse output setting mode.
Mode defines the ratio of current used for threshold value to judge stand-by power.
(Ratio for the rated current)
・
It is set the range of 0.1 to 100.0%.
Set it using <ITEM/
△
>,<SET>+<ITEM/
△
>.
(0.1 to 100.0)
Increase
Decrease
↓
<SET>
Stand-by alarm setting mode 2
*It is only when ‘AL-S’ is selected on unit for pulse output setting mode.
Mode defines the time used for threshold value to judge stand-by power.
・
It is set the range of 0 to 9999min.
When ‘0’ is set, alarm is always output at the time when judging the stand-by power.
When ‘1 to 9999’ is set, alarm is output at the time when passing the setting time with the stand-by
power.
The alarm can be reset by pressing <SET> with the instantaneous electric power display. After
reset the alarm, start to monitor the stand-by power again.
Set it using <ITEM/
△
>,<SET>+<ITEM/
△
>.
( 0 to 9999 min.)
Increase
Decrease
↓
<SET>
Preset value setting mode
*It is only when ‘Cnt’ is selected on unit for pulse output setting mode.
Mode defines count value used for output.
・
It is set the range of 0(0.000) to 999999(999.999).
*The range differs according to the pre-scale set by pre-scale setting mode.
Set it using <ITEM/
△
>,<SET>+<ITEM/
△
>.
( 0 to 999999)
Increase
Decrease
↓
<SET>