KW2G/ KW2G-H Eco-POWER METER
37
+
+
Unit for pulse output setting mode
Mode defines unit used for pulse output. It defines the unit of integrated electric power for
1-pulse output.
・
Select from 0.001/0.01/0.1/1/10/100kWh /AL-P/AL-C/AL-S/Cnt/OUT/Error.
When one of the ‘0.001/0.01/0.1/1/10/100’ [kWh] is set, one pulse is output at reaching the setting
value. When ‘AL-P(Power alarm)’ is set, alarm is output at the time when instantaneous electric
power is over the setting value. When ‘AL-C(Current alarm)’ is set, alarm is output at the time when
current is over the setting value. When ‘AL-S(Stand-by alarm)’ is set, alarm is output at the time
when current is under the setting value and it passes the setting time. When ‘Cnt(Count output)’ is
set, it output at the time when count value reaches preset value set by preset value setting mode.
When ‘OUT’ is set, it controls the output via communication.
When ‘Error (Error alarm)’ is set, alarm is output When SD memory card writing error, battery
shortage, communication error between main unit and expansion unit.
Press <ITEM/
△
>,<SET>+<ITEM/
△
> to change.
0.001
0.01
0.1
1
10
100
AL-P
AL-C
AL-S
AL-S
OUT
Error
↓
<SET>
Pulse output width setting mode
*It is only when ‘electric power value’ is selected
on unit for pulse output setting mode.
Mode defines pulse output width. It defines the width for 1 pulse.
・
It is set the range of 1 to 100ms.
Set it using <ITEM/
△
>, <SET>+<ITEM/
△
>.
(1
~
100 )
Increase
Decrease
↓
<SET>
Power alarm setting mode
*It is only when ‘AL-P’ is selected on unit for pulse output setting mode.
Mode defines instantaneous electric power used for alarm output.
・
It is set the range of 0.00 to 9999.99kW.
Set it using <ITEM/
△
>,<SET>+<ITEM/
△
>.
(0.00 to 9999.99)
Increase
Decrease
↓
<SET>
+
+
+
+
+
+
+
+
+
+