KW2G/ KW2G-H Eco-POWER METER
35
+
+
+
Simple measuring setting mode
Mode defines that you use simple measuring function or not.
Select ‘ON’ in order to use simple measuring function.
Press <ITEM/
△
> to change OFF
⇔
ON.
OFF
ON
↓
<SET>
Simple voltage setting mode
*It is only when ‘ON’ is selected on Simple measuring setting mode.
Mode defines voltage value to use for simple measuring.
・
It can be set the range of 0.0 to 9999.9V (initial:110.0V).
Ex.) If it is 220V, set to ‘220.0’.
Set it using <ITEM/
△
>, <SET>+<ITEM/
△
>.
(0.0 to 9999.9, initial:110.0)
Increase
Decrease
↓
<SET>
Simple PF setting mode
*It is only when ‘ON’ is selected on Simple measuring setting mode.
Mode defines power factor to use for simple measuring.
・
It can be set the range of 0.00 to 1.00 (initial:1.00).
Ex.) If it is 0.9, set to ‘0.90’.
Set it using <ITEM/
△
>, <SET>+<ITEM/
△
>.
(0.00 to 1.00)
Increase
Decrease
↓
<SET>
Cutoff current setting mode (
※
)
Mode defines load current that does not measure (Cutoff current).
Use to avoid miss-measurement by wiring or induction noise at no-load.
0.00kW is displayed for instantaneous electric power, 0.0A is displayed for current. Integrated
electric power is not added.
・
It can be set the range of 0.1 to 50.0%.
ex) When set to 10.0, current (=power) under 10.0%F.S is not added.
Set it using <ITEM/
△
>,<SET>+<ITEM/
△
>.
(0.1 to 50.0)
Increase
Decrease
↓
<SET>