Characters,
Factory Default
Setting Item, Function, Setting Range
EV2 alarm value 0 Enabled/Disabled
• When EV2 alarm value is 0 (zero), alarm action can be Enabled or Disabled.
Corresponds to [EV2 alarm value 0 Enabled/Disabled] in Initial setting mode.
• Selection item:
Disabled
Enabled
[A]
Available only when Event output EV2 is specified.
Available when
(Alarm output, High limit alarm) to
(Alarm output, High/Low limit range
independent alarm),
(Alarm output, High limit with standby alarm) to
(Alarm output, High/Low
limits with standby independent alarm) are selected in [Event output EV2 allocation].
EV2 alarm value
• Sets EV2 alarm value.
Corresponds to [EV2 alarm value] in Initial setting mode.
EV2 alarm value matches EV2 low limit alarm value in the following cases:
(Alarm output, High/Low limits independent alarm),
(Alarm output,
High/Low limit range independent alarm), or
(Alarm output, High/Low
limits with standby independent alarm) is selected in [Event output EV2 allocation].
• Setting range:
High limit alarm
-(Input span) to Input span
( )
(*1) (*2)
Low limit alarm
-(Input span) to Input span
( )
(*1) (*2)
High/Low limits alarm
0 to Input span
( )
(*1) (*2)
High/Low limits independent
alarm
0 to Input span
( )
(*1) (*2)
High/Low limit range alarm
0 to Input span
( )
(*1) (*2)
High/Low limit range
independent alarm
0 to Input span
( )
(*1) (*2)
Process high alarm
Input range low limit to Input range high limit
(*1) (*3)
Process low alarm
Input range low limit to Input range high limit
(*1) (*3)
High limit with standby alarm
-(Input span) to Input span
( )
(*1) (*2)
Low limit with standby alarm
-(Input span) to Input span
( )
(*1) (*2)
High/Low limits with standby
alarm
0 to Input span
( )
(*1) (*2)
High/Low limits with standby
independent alarm
0 to Input span
( )
(*1) (*2)
[B]
Available only when Event output EV2 is specified.
Available when any alarm from
(Alarm output, High limit alarm) to
(Alarm output, High/Low
limits with standby independent alarm) is selected in [Event output EV2 allocation].
[C]
EV2 high limit alarm value
• Sets EV2 high limit alarm value.
This value is available only for the following cases:
(Alarm output, High/Low limits independent alarm),
(Alarm
output, High/Low limit range independent alarm), or
(Alarm output,
High/Low limits with standby independent alarm) is selected in [Event output EV2
allocation].
Corresponds to [EV2 high limit alarm value] in Initial setting mode.
• Setting range: Same as those of EV2 alarm value
Available only when Event output EV2 is specified.
(*1) The placement of the decimal point follows the selection.
(*2) For DC voltage, current inputs, the input span is the same as the scaling span.
(*3) For DC voltage, current inputs, input range low (or high) limit value is the same as scaling low (or high) limit value.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]