6.2 Initial Setting Mode
To enter Initial setting mode, press and hold the
and
keys (in that order) for 3 seconds in RUN
mode.
To set (or select) each setting item, use the
or
key.
To register each setting item, press the
key.
Explanation of setting item:
• Upper left: PV Display: Indicates setting characters.
• Lower left: SV Display: Indicates factory default.
• Right side: Indicates the setting item, explanation of its function, and setting range (or selection item).
[1]
Input type
• Selects an input type from thermocouple (10 types), RTD (2 types), Direct current
(2 types) and DC voltage (4 types), and the unit
/ .
Setting item numbers such as [1], [2] are the same as those on Section “14. Key Operation Flowchart”
(p.131).
Characters,
Factory Default
Setting Item, Function, Setting Range
[1]
Input type
• Selects an input type from thermocouple (10 types), RTD (2 types), Direct current
(2 types) and DC voltage (4 type), and the unit
/ .
• When changing the input from DC voltage to other inputs, remove the sensor
connected to this controller first, then change the input. If the input is changed
with the sensor connected, the input circuit may break.
• When changing an input type, refer to Section “8.10 Items to be Initialized by
Changing Settings” (p.84).
• Selection item:
K
-200 to 1370
K
-328 to 2498
K
-200.0 to 400.0
K
-328.0 to 752.0
J
-200 to 1000
J
-328 to 1832
R
0 to 1760
R
32 to 3200
S
0 to 1760
S
32 to 3200
B
0 to 1820
B
32 to 3308
E
-200 to 800
E
-328 to 1472
T
-200.0 to 400.0
T
-328.0 to 752.0
N
-200 to 1300
N
-328 to 2372
PL-
0 to 1390
PL-
32 to 2534
C(W/Re5-26)
0 to 2315
C(W/Re5-26)
32 to 4199
Pt100
-200.0 to 850.0
Pt100
-328.0 to1562.0
JPt100
-200.0 to 500.0
JPt100 -328.0 to 932.0
Pt100
-200 to 850
Pt100
-328 to 1562
JPt100
-200 to 500
JPt100 -328 to 932
4 to 20 mA DC -2000 to 10000
0 to 20 mA DC -2000 to 10000
0 to 1 V DC
-2000 to 10000
0 to 5 V DC
-2000 to 10000
1 to 5 V DC
-2000 to 10000
0 to 10 V DC
-2000 to 10000
Setting characters
Factory default value
Setting item name, function, setting range (or selection item)