13.7 Engineering Mode 1
The PV Display indicates setting characters, and the SV Display indicates factory default value.
Characters,
Factory Default
Setting Item, Setting Range
Set value lock
Change via Keypad
Change via Software
Communication
Unlock
All set values can be changed.
All set values can be
Lock 1
None of the set values can be
changed.
changed.
Lock 2
In Fixed value control, only SV
and Alarm value can be changed.
In Program control, Step SV,
Step time and Alarm value can
be changed.
Lock 3
All set values can be changed.
Lock 4
None of the set values can be
changed.
Lock 5
In Fixed value control, only SV
and Alarm value can be changed.
In Program control, Step SV,
Step time and Alarm value can
be changed.
Setting items – except Input
type, Controller/Converter –
can be changed temporarily
via software communication.
However, if power is turned
ON again, the set values
revert to the values before
Lock 3, 4 or 5 was selected.
Event output EV1 allocation
[Event Output Allocation Table]
No event
Alarm output, High limit alarm
Alarm output, Low limit alarm
Alarm output, High/Low limits alarm
Alarm output, High/Low limits independent alarm
Alarm output, High/Low limit range alarm
Alarm output, High/Low limit range independent alarm
Alarm output, Process high alarm
Alarm output, Process low alarm
Alarm output, High limit with standby alarm
Alarm output, Low limit with standby alarm
Alarm output, High/Low limits with standby alarm
Alarm output, High/Low limits with standby independent
alarm
Loop break alarm output
Time signal output
Output during AT
Pattern end output
Output by communication command