13.4 Initial Setting Mode
The PV Display indicates setting characters, and the SV Display indicates factory default value.
Characters,
Factory Default
Setting Item, Setting Range
Input type
K
-200 to 1370
K
-328 to 2498
K
-200.0 to 400.0
K
-328.0 to 752.0
J
-200 to 1000
J
-328 to 1832
R
0 to 1760
R
32 to 3200
S
0 to 1760
S
32 to 3200
B
0 to 1820
B
32 to 3308
E
-200 to 800
E
-328 to 1472
T
-200.0 to 400.0
T
-328.0 to 752.0
N
-200 to 1300
N
-328 to 2372
PL-
0 to 1390
PL-
32 to 2534
C(W/Re5-26)
0 to 2315
C(W/Re5-26) 32 to 4199
Pt100
-200.0 to 850.0
Pt100
-328.0 to 1562.0
JPt100 -200.0 to 500.0
JPt100 -328.0 to 932.0
Pt100
-200 to 850
Pt100
-328 to 1562
JPt100 -200 to 500
JPt100 -328 to 932
4 to 20 mA DC -2000 to 10000
0 to 20 mA DC -2000 to 10000
0 to 1 V DC
-2000 to 10000
0 to 5 V DC
-2000 to 10000
1 to 5 V DC
-2000 to 10000
0 to 10 V DC -2000 to 10000
Scaling high limit
Setting range: Scaling low limit value to input range high limit value
DC voltage, current inputs: -2000 to 10000
(*1)
Scaling low limit
Setting range: Input range low limit value to scaling high limit value
DC voltage, current inputs: -2000 to 10000
(*1)
Decimal point place
No decimal point
1 digit after decimal point
2 digits after decimal point
3 digits after decimal point
(*1) The placement of the decimal point follows the selection.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]