Characters,
Factory Default
Setting Item, Function, Setting Range
EV2 alarm Energized/De-energized
• Selects Energized/De-energized status for EV2 alarm.
(Refer to ‘EV1/EV2 Energized/De-energized’ on p.40.)
• Selection item:
Energized
De-energized
[F]
Available only when Event output EV2 is specified.
Available when any alarm from
(Alarm output, High limit alarm) to
(Alarm output, High/Low
limits with standby independent alarm) is selected in [Event output EV2 allocation].
[G]
TS2 output step number
• Sets the step number at which Time signal output TS2 will be turned OFF or ON
during Program control.
(Refer to ‘Time Signal Output’ on p.41.)
• Setting range: 1 to 9
Available only when
(Time signal output) is selected in [Event output EV2 allocation].
[H]
TS2 OFF time
• Sets Time signal output TS2 OFF time.
(Refer to ‘Time Signal Output’ on p.41.)
• Setting range: 00:00 to 99:59
(*4)
Available only when
(Time signal output) is selected in [Event output EV2 allocation].
[I]
TS2 ON time
• Sets Time signal output TS2 ON time.
(Refer to ‘Time Signal Output’ on p.41.)
• Setting range: 00:00 to 99:59
(*4)
Available only when
(Time signal output) is selected in [Event output EV2 allocation].
[7]
Loop break alarm time
• Sets the time to assess the Loop break alarm.
Refer to ‘Loop Break Alarm’ on p.40.
• Setting range: 0 to 200 minutes
Setting to 0 (zero) disables the alarm.
[8]
Loop break alarm span
• Sets the temperature to assess the Loop break alarm.
Refer to ’Loop Break Alarm’ on p.40.
• Setting range: 0 to 150
( ), or 0.0 to 150.0
( )
DC voltage, current inputs: 0 to 1500
(*1)
Setting to 0 (zero) disables the alarm.
(*4) Time unit follows the selection from [Step time unit].