5-15
5.7.3 Replacement of Backup Battery
The procedure for replacing the backup battery is as follows.
Procedure
1. Supply power to the control unit for more than five minutes.
Charge the built-in capacitor to retain the contents of the memory during the replacement of the battery.
2. Turn off the power supply.
When the power is off, supply the power to the control unit for more than five minutes to charge the built-
in capacitor to back up the memory during the replacement of the battery.
3. Remove the expansion cover located at the surface of the control unit.
4. Remove the used battery.
5. Install a new battery within two minutes after turning off the power.
6. Install the expansion cover.
Note:
If the power is not sufficiently supplied or it takes too much time to replace the battery, retained memory
data may be lost.
5.7.4 Lifetime and Time for Replacement of Backup Battery
Battery lifetime
Type of control unit
Battery lifetime
Suggested replacement interval
L40, L60
4.6 years or more
7 years
Note1) The battery lifetime is the value when no power at all is supplied.
Note2) Note that the lifetime may be shorter than the typical lifetime depending on the use conditions.
Note3) The battery is used for the battery detection circuit even when power is supplied. The lifetime is
about twice as long as that when no power is supplied.
Detection of battery error and time for replacement
-
Special internal relays R9005 and R9006 will go on if the battery voltage drops. Create a program to
announce errors to the outside as necessary.
-
When the system register No.4 "Battery Error Alarm" is enabled, the ERR.LED of the control unit will
flash.
-
Although data will be retained for about a week after the detection of battery error without power, the
battery should be replaced as soon as possible.
Note:
-
If a week has passed without power after the special internal relays R9005 and R9006 turned on or the
ERR.LED flashed, retained memory data may be lost.
-
Regardless of how much time has passed after the detection of battery error, supply power to the
control unit for more than five minutes before replacing the battery.
-
Special internal relays R9005 and R9006 will be on when a battery error is detected regardless of the
setting of system register No.4.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X0 L14R
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 18: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 48: ...4 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 118: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 154: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 196: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 210: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 288: ...14 7 ASCII Codes Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 289: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...