12-3
Power supply specifications
Item
Specifications
Rated voltage
100 to 240 V AC
Voltage regulation range
85 to 264 V AC
Inrush current
L14: 35A or less (at 240 V AC, 25
C)
L30/L40/L60: 40A or less (at 240 V AC, 25
C)
Momentary power off time
10 ms (when using 100 V AC)
Frequency
50/60 Hz (47 to 63 Hz)
Leakage current
0.75 mA or less between input and protective earth terminals
Internal power supply part
Guaranteed life
20,000 hours (at 55
C)
Fuse
Built-in (Cannot be replaced)
Insulation system
Transformer insulation
Terminal screw
M3
Service Power Supply for Input (Output) (For L30/L40/L60)
Item
Specifications
Rated output voltage
24 V DC
Voltage regulation range
21.6 to 26.4 V DC
Rated output current
0.3 A
Overcurrent protection function
Note)
Available
Terminal screw
M3
Note) This is a function to protect overcurrent temporarily. If a current load that is out of the
specifications is connected, it may lead to damages.
Unit’s current consumption table
Unit type
Current consumption of power supply
for Control unit
100 V AC
200 V AC
Control unit
AFPX-L14R
100 mA or less
70 mA or less
AFPX-L30R
330 mA or less
210 mA or less
AFPX-L40R
350 mA or less
220 mA or less
AFPX-L40MR
350 mA or less
220 mA or less
AFPX-L60R
390 mA or less
250 mA or less
AFPX-L60MR
390 mA or less
250 mA or less
Expansion I/O unit
AFPX-E16R
Note1)
65 mA or less
40 mA or less
AFPX-E30R
Note2)
310 mA or less
210 mA or less
AFPX-E16T
Note1)
20 mA or less
10 mA or less
AFPX-E16P
Note1)
30 mA or less
15 mA or less
AFPX-E30T
Note2)
345 mA or less
220 mA or less
AFPX-E30P
Note2)
350 mA or less
225 mA or less
AFPX-E16X
Note1)
20 mA or less
10 mA or less
AFPX-E14YR
Note1)
75 mA or less
40 mA or less
Programmable display
GT02,GT02L
(5 VDC,RS232C type)
25 mA or less
15 mA or less
Note1) These current consumption indicate the increased amount of the current consumption of the
cc
control unit.
Note2) The current consumption of E30 is the current consumption at the supply terminal of E30. The
current consumption of the control unit does not increase.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X0 L14R
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 18: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 48: ...4 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 118: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 154: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 196: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 210: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 288: ...14 7 ASCII Codes Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 289: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...