14.1.2 Table of System Registers for FP-X0 L14 / L30 / L40 / L60
Item
Add-
ress
Name
Default
value
Description
H
ol
d/
N
on
-ho
ld
1
5
Starting number setting for counter
L14/L30:250
L40/l60:1008
L14/L30 : 0 to 256
L40/L60 : 0 to 1024
6
Hold type area starting number
setting for timer and counter
►
For L40/L60
1008
0 to 1024
7
Hold type area starting number
setting for internal relays
►
For L40/L60
248
0 to 256
8
Hold type area starting number
setting for data registers
►
For L40/L60
7890
0 to 8192
14
Hold or non-hold setting for step
ladder process
►
For L40/L60
Non-hold
Hold/
Non-hold
4
Previous value is held for a leading
edge detection instruction (DF
instruction) with MC
Hold
Hold/
Non-hold
H
ol
d/
N
on
-ho
ld
2
10
Hold type area starting word No. for
PC(PLC) link relay (For PC(PLC)
link 0)
►
For L40/L60
64
0 to 64
11
Hold type area starting word No. for
PC(PLC) link relay (For PC(PLC)
link 1)
►
For L40/L60
128
64 to 128
12
Hold type area starting word No. for
PC(PLC) link register (For PC(PLC)
link 0)
►
For L40/L60
128
0 to 128
13
Hold type area starting word No. for
PC(PLC) link register (For PC(PLC)
link 1)
►
For L40/L60
256
128 to 256
A
c
ti
o
n
o
n
e
rro
r
20
Disable or enable setting for
duplicated output
Disabled
Disabled/Enabled
23
Operation setting when an I/O
verification error occurs
Stop
Stop/Continuation of operation
26
Operation setting when an
operation error occurs
Stop
Stop/Continuation of operation
T
im
e
s
et
ti
n
g
31
Wait time setting for multi-frame
communication
2600.0 ms
4 to 32760 ms
32
Timeout setting for SEND/RECV,
RMRD/RMWT commands
10000.0 ms
10 to 81900 ms
34
Constant value settings for scan
time
Normal scan
0: Normal scan
0 to 600 ms: Scans once each
specified time interval
Note1) Data is retained only when installing a backup battery.
Note2) Without the battery, use at the default settings. If changing the settings, the "Hold/Non-hold"
operation becomes unstable.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Summary of Contents for FP-X0 L14R
Page 1: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 10: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 18: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 48: ...4 6 Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 118: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 154: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 196: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 210: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 288: ...14 7 ASCII Codes Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...
Page 289: ...Phone 800 894 0412 Fax 888 723 4773 Web www clrwtr com Email info clrwtr com ...