Http Server Functions/ Web Pages
FP Web-Server V2.11
78
Display on the HTML editor (Netscape Composer):
Display on the browser (Netscape Browser):
The setup of the field for PLC data display always has the format
{TTxxxy_aa_bb}
with the
following parameters:
TT
PLC Data Type. Implemented PLC data identifiers:
DT, FL, LD, R, X, Y
xxxy
Address of the PLC Data, e.g. DT200 or Y7.
The address range supported by the FP Web-Server is 0 ... 32765.
For internal relays, the last position of the address is a hexadecimal number from 0...F, e.g. R2F
aa
Numbers: Number of characters reserved in HTML. The rest will be cut off.
Internal Relays: Text that should be displayed at internal relay state 0, e.g.
OFF
.
bb
Numbers: Number format, i.e. type of the display. See below.
Internal Relays: Text that should be displayed at internal relay state 1, e.g.
ON
.
The data type and address part
TTxxxy
can be replaced by the corresponding variable name
(see page 82) from the FPWIN Pro project, e.g.
{'VarName'_aa_bb}
or
{'name'_5_i}
.
There is no space allowed between the curly bracket and the first character. For example
{
DT3_4_u}
or
{ 'name'_5_i}
is not allowed. It will be interpreted as a Java Script (see page 95)
command and copied unchanged into the final HTML file.
The setup of the format specification bb for numbers is
[flags][width][.precision][l]type
Only the specification 'type' is obligatory. The other inputs are optional. In the following list the
corresponding FPWIN Pro types are listed in brackets:
Summary of Contents for FP Web-Server
Page 3: ......
Page 11: ......
Page 12: ...Chapter 1 Getting Started...
Page 21: ...Getting Started FP Web Server V2 11 10 1 6 FP Web Server Block Diagram...
Page 23: ......
Page 24: ...Chapter 2 Hardware Description...
Page 41: ......
Page 42: ...Chapter 3 First Steps...
Page 55: ......
Page 56: ...Chapter 4 Configurator Software...
Page 61: ......
Page 62: ...Chapter 5 Base Configuration...
Page 66: ...Chapter 6 Email Setup...
Page 80: ...Chapter 7 Http Server Functions Web Pages...
Page 113: ......
Page 114: ...Chapter 8 Ethernet RS232C Ports...
Page 119: ......
Page 120: ...Chapter 9 Dial In Setup for PPP Server...
Page 125: ...Dial In Setup for PPP Server FP Web Server V2 11 114...
Page 127: ...Dial In Setup for PPP Server FP Web Server V2 11 116...
Page 139: ......
Page 140: ...Chapter 10 Dial Out Setup for PPP Client...
Page 150: ...Chapter 11 NTP Server for PLC Clock Synchronization...
Page 153: ......
Page 154: ...Chapter 12 Modbus Functions...
Page 162: ...Chapter 13 IEC 60870 Functions of the FP Web Server...
Page 168: ...Chapter 14 Java Applet Library MEW JAR...
Page 170: ...Chapter 15 Additional Information...