Email Setup
FP Web-Server V2.11
58
"PLC control relay":
The PLC internal relay Rxy is prompted by the FP Web-Server and is set by the PLC in case an
email has to be sent. Rxy is reset by the FP Web-Server after the email has been sent.
If an error occurs, the Rxy+1 is set by the FP Web-Server after the email transmission.
Otherwise the Rxy+1 will be reset.
This setting also has to correspond to the PLC Program (see page 61).
"DT PLC address register":
PLC 16-bit DT Address DTzz: For sending the email, the value (
Content
) of the storage location
DTzz is read by the FP Web-Server and interpreted as a DT address (
Pointer
), where the string
(an FPWIN Pro string with a header) with the recipient's email address begins. If the value of the
DTzz lies in the range of 0 to 3, the Recipient's Address defined in the Configurator project is
used.
DTzz+1: For sending an email, the value (
Content
) of the storage location DTzz+1 is read by
the FP Web-Server and interpreted as a DT address (
Pointer
), where the string (an FPWIN Pro
string with a header) with the recipient's email address begins. If the value of the DTzz lies in the
range of 0 to 3, the email text defined in the Configurator project is sent (see below).
Data in the FL range cannot be used!
This setting also has to correspond to the PLC program (see page 61).
"Poll time delay":
After the time interval has been predefined (for example every 7 seconds), the FP Web-Server
checks the internal relay PLC Control Relay of the PLC (via MEWTOCOL) to find out if the PLC
wants to send an email.
The "Poll time delay" works in the range of 1 to 60 seconds.
This interval has to agree with the
"Server_Timeout"
definition in the global variables of the
PLC Program (see page 61).
"Email recipient address: x":
Predefined email address of the recipient No.0 to No.3: With the [Spin] buttons (arrow up/ down)
you can choose among the 4 input fields for the recipient's addresses.
Always enter the predefined email address of the recipient with <> characters!
Umlauts and Japanese characters are not allowed.
A recipient's address can be selected by using the numbers 0 to 3 in the PLC Program (see
page 61).
"Automatic TO and FROM keywords":
With these check boxes are selected, the FP Web-Server automatically inserts the keywords
"To" and "From". For details, please refer to the online help under the keyword "Automatic
TO/FROM tag insertion".
"Email text number: x":
Predefined email texts (see page 59) No.0 to No.3:
Summary of Contents for FP Web-Server
Page 3: ......
Page 11: ......
Page 12: ...Chapter 1 Getting Started...
Page 21: ...Getting Started FP Web Server V2 11 10 1 6 FP Web Server Block Diagram...
Page 23: ......
Page 24: ...Chapter 2 Hardware Description...
Page 41: ......
Page 42: ...Chapter 3 First Steps...
Page 55: ......
Page 56: ...Chapter 4 Configurator Software...
Page 61: ......
Page 62: ...Chapter 5 Base Configuration...
Page 66: ...Chapter 6 Email Setup...
Page 80: ...Chapter 7 Http Server Functions Web Pages...
Page 113: ......
Page 114: ...Chapter 8 Ethernet RS232C Ports...
Page 119: ......
Page 120: ...Chapter 9 Dial In Setup for PPP Server...
Page 125: ...Dial In Setup for PPP Server FP Web Server V2 11 114...
Page 127: ...Dial In Setup for PPP Server FP Web Server V2 11 116...
Page 139: ......
Page 140: ...Chapter 10 Dial Out Setup for PPP Client...
Page 150: ...Chapter 11 NTP Server for PLC Clock Synchronization...
Page 153: ......
Page 154: ...Chapter 12 Modbus Functions...
Page 162: ...Chapter 13 IEC 60870 Functions of the FP Web Server...
Page 168: ...Chapter 14 Java Applet Library MEW JAR...
Page 170: ...Chapter 15 Additional Information...