This document describes the functional details of the Remote Controller for Window Air Conditioner. The receiver 
unit receives command from the user (By Remote Transmitter or Keys on the Receiver Board) and takes action 
accordingly by processing the received command in order to control the various sub units of the air conditioner.

The controller receiver has following general features

 

Preset temperature setting from 16°C  to 30°C

 

Visual indication of the system configuration using LEDs and seven segment display.

 

Various modes of operation   (Explained below under the heading 'Modes Of Operations')

 

NOTE: Power box cabinet: FR material.

There are 11 LEDs on the Receiver board (Front display panel) to indicate the following.

 

Power 

:  To indicate Supply in System

 

Cool 

:   To indicate the Cool mode selection & Compressor Status.

 

Dry 

:   To indicate the Dry mode selection

 

Fan 

:   To indicate the Fan mode selection

 

Swing 

:   To indicate Swing motor condition.

 

Fan Low/ Medium/High  :   To indicate Fan Speed.

 

Timer 

:   To indicate Timer setting.

 

Powerful 

:   To indicate Powerful selection condition.

 

Sleep 

:   To indicate Sleep condition.

-: 4 :-

OPERATIONAL INSTRUCTIONS

INTRODUCTION

GENERAL FEATURES

DISPLAY

The Seven Segment shows:

 

Set Temperature (ST) in Cool Mode and Dry Mode.

 

'Fn' in Fan Mode.

 

'E1' when Room Sensor Short or Open.

 

'E2' when Coil Sensor Short or Open.

 

“SL” for Sleep in Cool Mode only for 5 second in every one minute if Sleep is active.

 

‘CL’ visible only when operated from Display Panel button.

 

 ‘dr’  visible only when operated from Display Panel button.

 

‘Po’  visible only when operated from Display Panel button.

Various modes of operation of the unit are as follows:
 

Cool

 

Dry

 

Fan

Cool :

 

In this mode of operation, compressor will be switched on after a delay of three minute depending on the 

  differential of Room Temp &   Set Temperature.

 

Cool LED blinks during the ON delay time of the compressor.

 

Preset temperature and fan speed can be changed by the user.

 

Fan Speed can be selected (Fan auto, High, Medium or Low).

 

Compressor will work as per the following conditions:

 

Compressor will cut off,

 

 

If Room temperature = Preset temperature - 1ºC or Below

 

Compressor will cut in,

 

 

If Room temperature = Preset tempe 1° C or Above

NOTE: Compressor should take 3 min times delay if it required as per the timing protection and 3mins required 

for thermostatic cutoff from Comp Switch On (minimum Run Time).

Dry :

Initial startup 
Fan motor run at only low speed and cannot be changed. The comp On/Off duration is controlled by difference 
between room temp and set temp. as follows:
 

Room Temp = Set Temp + 2ºC or above 

 

Comp On for 15 min Off for 5min

 

Room Temp = Set Temp + 1ºC 

 

 

Comp On for 10 min Off for 10min

 

Room Temp = Set Temp 

 

 

Comp On for 10 min Off for 10min

 

Room Temp = Set Temp-1ºC 

 

 

Comp On for 10 min Off for 10min

 

Room Temp = Set Temp -2ºC or Below 

 

Comp On for 5 min Off for 15min

DUAL DIGIT 7 SEGMENT DISPLAY

MODES OF OPERATIONS

Summary of Contents for CW-XN181AM Series

Page 1: ...r Thank you for purchasing Panasonic Air Conditioner Installation instructions attached Before operating the unit read these operating instructions thoroughly and keep them for future reference Englis...

Page 2: ......

Page 3: ...TURES Display Panel 3 Remote Control 3 Operational Instructions 4 5 Preparation Before Operation 6 Air conditioner Installation 7 10 Air conditioner Operation 11 12 Energy Saving Hints 13 Care and Mai...

Page 4: ...se injury Do not try to repair unit yourself Plug in properly before operating and use a specified power cord If abnormal conditions burnt smell etc occur switch off and remove the power plug Confirm...

Page 5: ...oor Side 7 Air Outlet Grille 8 Electronic Control Keypad 9 Power Supply Cord 10 Vertical Vane 2 10 4 9 8 1 3 5 7 6 Precaution for using R32 refrigerant The basic installation work procedures are the s...

Page 6: ...ignal from the remote control 3 User has to refer the photo and feature of same remote shown above which they receive with AC FEATURES Maximum distance 7meters Fan Speed Air Swing Timer On Fan Speed B...

Page 7: ...in Cool Mode only for 5 second in every one minute if Sleep is active CL visible only when operated from Display Panel button dr visible only when operated from Display Panel button Po visible only wh...

Page 8: ...y changing Mode Timer Used to set timer ON when unit is OFF and vice versa Sleep Sleep function can be selected in cool mode only Total 2 degree preset temperature will increment in 8 hour 1 degree in...

Page 9: ...rformance If operation is stopped and to be restarted immediately the unit will resume operation only after 3 minutes ABOUT THE BATTERIES The batteries can be used for approximately one year Be sure t...

Page 10: ...hes towards the back for optimum performance For optimum performance Drain should be plugged For testing purpose and enhanced performance use the Installation guidelines given below INSTALLING THE UNI...

Page 11: ...o the cabinet Lock the chassis to the cabinet with screws LN Series from left 1 nos and right 1 nos side XN Series from back side 2 nos Tilt down for better drainage max 10mm Secure it with wood screw...

Page 12: ...Always use at the rated voltage and with a specific air conditioning circuit This equipment must be earthed and strongly recommended to be installed with Earth Leakage Circuit Breaker ELCB or Residen...

Page 13: ...mum cooling efficiency the airconditioner is designed to splash the condensation water on the condenser coil In order to avoid the splashing sound an external drain can be provided by using the follow...

Page 14: ...ose the speed level of the fan The indicator will light up and the beep sound will indicate changing setting NOTE The latest fan speed setting will be memorized and the indicator will light up the nex...

Page 15: ...cancelled manually or due to power failure you can restore the previous setting once power is resumed by pressing Set SET SETTING THE SLEEP MODE SLEEP SLEEP To Maximize comfort while sleeping This op...

Page 16: ...urs the timer setting is cancelled Once power returns reset the timer O Setting the temperature 1 C higher save 10 electricity costs Clean the air filter every 2 weeks Regular cleaning of the air filt...

Page 17: ...wasted NOTE Do not dry the front panel or the air filter in direct sunlight Exposure to direct sunlight may discolour or deform the panel Always turn off the air conditioner and the main power supply...

Page 18: ...is impede by curtains or furniture After 15 minutes of operation it is normal for the temperature difference between intake and outlet air to be more O than 8 C for cooling Humidity is high Condensed...

Page 19: ......

Page 20: ...ACW4PR18901 Refer to operating instruction for handling of End of Life Products...

Reviews: