87
12.4. Emergency operation
When using the wireless remote control and losing the remote controller, emergency operation can be operated by pressing auto
button in the receiver.
•
Press the auto button continuously within 5 seconds
If there is an abnormality in the temperature thermistor (disconnect or shorted), indoor unit cannot be operated.
If abnormality detected in the indoor or outdoor unit, turn off the main power supply and find the cause.
Check the resistance of each thermistor of both indoor and outdoor units by referring the resistance table as follows.
Thermistor resistance table
Press the auto button continuously within 5 seconds
→
emergency operation
• Press the auto button continuously for more than 5 seconds to less than 8 seconds
→
cooling test operation
• Press the auto button continuously for more than 8 seconds to less than 11 seconds
→
cooling test operation
Press the auto button continuously for more than 11 seconds to less than 16 seconds
→
set remote controller address
Press the auto button continuously for more than 16 seconds to less than 21 seconds
→
remote controller address confirmation mode
Press the auto button continuously for more than 21 seconds to less than 26 seconds
→
change address of branch unit
Press the auto button continuously for more than 26 seconds to less than 31 seconds
→
individual change mode
During the above each stage, finally press the SET button, then the operation mode can be decided.
Resistance value (k
Ω
)±5%
Temperature
Indoor
Outdoor
°
C
Room temperature
Pipe temperature
Discharge temperature
Pipe temperature
thermistor
thermistor
thermistor
thermistor
-20
158.5
211.3
528.3
47.9
-10
87.5
116.7
291.8
27.1
-5
66.1
88.2
220.5
20.7
0
50.5
67.3
168.3
15.9
5
38.9
51.9
129.8
12.4
10
30.3
40.4
100.9
9.8
15
23.8
31.7
79.2
7.7
20
18.8
25.1
62.7
6.2
25
15
20
50
5
30
12.1
16.1
40.2
4
40
8
10.6
26.5
2.7
50
5.4
7.2
17.9
1.9
60
3.7
5
12.4
1.3
Summary of Contents for CU-B14DBE5
Page 11: ...11 4 Dimensions 4 1 CS F18DTE5 ...
Page 12: ...12 4 2 CU J18DBE5 ...
Page 13: ...13 5 Refrigeration Cycle 5 1 CS F18DTE5 CU J18DBE5 ...
Page 14: ...14 6 Block Diagram 6 1 CS F18DTE5 6 2 CU J18DBE5 ...
Page 15: ...15 7 Wiring Diagram 7 1 CS F18DTE5 ...
Page 16: ...16 7 2 CU J18DBE5 ...
Page 18: ...18 8 2 Remote Control Display ...
Page 19: ...19 8 3 Remote Control Panel ...
Page 95: ...95 13 3 Reaching distance CS F18DTE5 Cooling ...
Page 96: ...96 13 4 Sound data ...
Page 97: ...97 13 5 Sound measuring point 13 5 1 Indoor Unit 13 5 2 Outdoor Unit ...
Page 100: ...100 14 Exploded View Indoor Unit 14 1 CS F18DTE5 ...
Page 101: ...101 14 2 CS F18DTE5 ...
Page 102: ...102 14 3 CS F18DTE5 ...
Page 105: ...105 16 Exploded View Outdoor Unit 16 1 CU J18DBE5 ...
Page 106: ...106 16 2 CU J18DBE5 ...
Page 108: ...108 18 Print Pattern 18 1 Indoor Unit Printed Main ...