49
10.5.7.
Heat insulation
10.5.8.
Charging with refrigerant
1.5 HP • 2 HP (14 • 18 type)
• At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 20m. If the
equivalent pipe length used will be 20m or less, no additional charging will be necessary.
• If the equivalent pipe length will be between 20 and 30m, charge with additional refrigerant according to the equivalent length
given in the table below.
2.5 HP ~ 6 HP (24 ~ 50 type)
• At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 30m. If the
equivalent pipe length used will be 30m or less, no additional charging will be necessary.
• If the equivalent pipe length will be between 30 and 50m, charge with additional refrigerant according to the equivalent length
given in the table below.
• Pump down operation
- Operate the pump down according to the following procedures.
10.5.9.
Electrical wiring
• Connect the power supply wiring and indoor/outdoor unit connection wiring according to the electrical circuit diagram instruc-
tions.
• Clamp the wires securely to the terminal connections using cord clamps so that no undue force is placed on the wires.
• Once all wiring work has been completed, tie the wires and cords together with the binding strap so that they do not touch other
parts such as the compressor and pipes.
Caution
Use a material with good heat-resistant properties as the
heat insulation for the pipes. Be sure to insulate both the
gas-side and liquid-side pipes. If the pipes are not ade-
quately insulated, condensation or water leakages may
occur.
Liquid-side pipes
Material that can withstand
Gas-side pipes
120
°
C or higher
Model
Additional charging amount
Equivalent length
1.5 HP • 2 HP (14 • 18 type)
0.02 kg/m
30m
2.5 HP ~ 6 HP (24 ~ 50 type)
0.05 kg/m
50m
Procedure
Notes
1. Confirm the valve on the liquid side and the gas side is surely open.
2. Press the PUMP DOWN switch on outdoor printed board for 1 second
or more.
Perform the cooling operation for five minutes or more.
3. Shut the valve on the liquid side surely.
When the valve is shut halfway, the compressor is occasionally dam-
aged.
The units must be connected to the supply cables for fixed wiring by qualified technician.
Feed the power source to the unit via a distribution switch board designed for this purpose, the switch should disconnected all
poles with a contact separation of at least 3mm.
When the supply cable is damaged, it must be replaced by qualified technician.
Warning
Be sure to install a current leakage breaker, main switch and fuse to the main power supply, otherwise electric shocks may result.
Be sure to connect the unit to secure earth connection.
If the earthing work is not carried out properly, electric shocks may result.
Wiring shall be connected securely by using specified cables and fix them securely so that external force of the cables may not
transfer to the terminal connection section.
Imperfect connection and fixing leads to fire, etc.
Summary of Contents for CU-B14DBE5
Page 11: ...11 4 Dimensions 4 1 CS F18DTE5 ...
Page 12: ...12 4 2 CU J18DBE5 ...
Page 13: ...13 5 Refrigeration Cycle 5 1 CS F18DTE5 CU J18DBE5 ...
Page 14: ...14 6 Block Diagram 6 1 CS F18DTE5 6 2 CU J18DBE5 ...
Page 15: ...15 7 Wiring Diagram 7 1 CS F18DTE5 ...
Page 16: ...16 7 2 CU J18DBE5 ...
Page 18: ...18 8 2 Remote Control Display ...
Page 19: ...19 8 3 Remote Control Panel ...
Page 95: ...95 13 3 Reaching distance CS F18DTE5 Cooling ...
Page 96: ...96 13 4 Sound data ...
Page 97: ...97 13 5 Sound measuring point 13 5 1 Indoor Unit 13 5 2 Outdoor Unit ...
Page 100: ...100 14 Exploded View Indoor Unit 14 1 CS F18DTE5 ...
Page 101: ...101 14 2 CS F18DTE5 ...
Page 102: ...102 14 3 CS F18DTE5 ...
Page 105: ...105 16 Exploded View Outdoor Unit 16 1 CU J18DBE5 ...
Page 106: ...106 16 2 CU J18DBE5 ...
Page 108: ...108 18 Print Pattern 18 1 Indoor Unit Printed Main ...