30
10 Installation Instruction
10.1. Pipe length
•
CORRECTION OF CAPACITIES
1. Correction of capacities according to the connecting pipe length.
The data of rated capacities (marked on the name plate) are based on 7.5 meters connecting pipe and horizontal installation.
2. For other pipe length of other installation multiply by the following correction factor to determine the revised cooling capacity.
Note :
Piping elevation B = outdoor unit installed at top
Piping elevation C = outdoor unit installed at bottom
10.2. Refrigerant additional charge
1.
Piping installation by standard piping
• At the time of shipment from the factory, this unit is charged with enough refrigerant for an equivalent pipe length of 20m.
(Refer the following table)
But when the piping length exceeds 20m, additional charge is required according to the following table.
Example:
CU-J18DBE5
In case of 30m long pipe (one way), the amount of refrigerant to be replenished is: (30 - 20) x 20 = 200g
Piping Size / Length & Elevation
Model No.
Piping size
Piping
length
(A)
Piping
elevation
(B)
Piping
elevation
(C)
Piping
Chargeless
Add
Refrigerant
Liquid /
High
Valve
Gas /
Low
Valve
Max(m)
Max(m)
Max(m)
Max(m)
(g/m)
R
Cassette
4
type
1
CS-F18DTE5
6.35
3-ways
12.70
3-ways
30
20
20
20
20
0
A
Model Name
Standard piping specification
Liquid piping
(dia.mm)
Gas piping
(dia.mm)
Gas chargeless
length (m)
Additional gas
volume (g/m)
CU-J18DBE5
6.35
12.7
20
20
Summary of Contents for CU-B14DBE5
Page 11: ...11 4 Dimensions 4 1 CS F18DTE5 ...
Page 12: ...12 4 2 CU J18DBE5 ...
Page 13: ...13 5 Refrigeration Cycle 5 1 CS F18DTE5 CU J18DBE5 ...
Page 14: ...14 6 Block Diagram 6 1 CS F18DTE5 6 2 CU J18DBE5 ...
Page 15: ...15 7 Wiring Diagram 7 1 CS F18DTE5 ...
Page 16: ...16 7 2 CU J18DBE5 ...
Page 18: ...18 8 2 Remote Control Display ...
Page 19: ...19 8 3 Remote Control Panel ...
Page 95: ...95 13 3 Reaching distance CS F18DTE5 Cooling ...
Page 96: ...96 13 4 Sound data ...
Page 97: ...97 13 5 Sound measuring point 13 5 1 Indoor Unit 13 5 2 Outdoor Unit ...
Page 100: ...100 14 Exploded View Indoor Unit 14 1 CS F18DTE5 ...
Page 101: ...101 14 2 CS F18DTE5 ...
Page 102: ...102 14 3 CS F18DTE5 ...
Page 105: ...105 16 Exploded View Outdoor Unit 16 1 CU J18DBE5 ...
Page 106: ...106 16 2 CU J18DBE5 ...
Page 108: ...108 18 Print Pattern 18 1 Indoor Unit Printed Main ...