16
English
5. Wiring Instructions
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring
closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each unit, with a power supply disconnect and leakage
breaker/fuse link for overcurrent protection provided in the exclusive line.
Circuit breaker must be in corporated in the fixed wiring in accordance with the wiring regulations. The circuit
breaker must be an approved 25 A, having a contact separation in all poles.
(3) To prevent possible hazard due to insulation failure, the unit must be grounded.
(4) Each wiring connection must be done tightly and in accordance with the wiring system diagram. Wrong wiring may
cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a
result of such unauthorized changes.
5-2. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local
electrical codes. Carefully observe these regulations when carrying out the installation.
Table 6 shows maximum wire lengths for control line and power line and fuse or circuit capacity.
Refer to the wiring system diagram (Fig. 25) for the meaning of (A), (B) and (C) in Table 6.
Type designation 245 IEC 57 (H05RN-F, GP85PCP etc.) or heavier cord.
NOTE
Table 6
Cross-Sectional
Area (mm
2
)
Max. Control Line Length (m)
(B) (C)
Max. Power Line Length (m)
(A)
Fuse
or
Circuit Capacity
Model
3.5
1.0
CU-5E34NBE
26
30
25 A
WARNING
�
Be sure to comply with local codes on running
the wire from the indoor unit to the outdoor unit
(size of wire and wiring method, etc.).
�
Each wire must be firmly connected.
�
No wire should be allowed to touch refrigerant
tubing, the compressor, or any moving part.
�
Be sure to connect power wires correctly
matching up numbers on terminals of the
outdoor unit and respective indoor units A – E.
CAUTION
�
Be sure to connect the power supply line to the outdoor unit as
shown in the wiring diagram. The indoor unit draws its power from
the outdoor unit.
�
Do not run wiring for antenna, signal, or power lines of television,
radio, stereo, telephone, security system, or intercom any closer
than 1 meter from the power cable and wires between the indoor
and outdoor units. Electrical noise may affect the operation.
�
To avoid the risk of electric shock, each air
conditioner unit must be grounded.
�
For the installation of a grounding device,
please observe local electrical codes.
�
Grounding is necessary, especially for units
using inverter circuits, in order to release
charged electricity and electrical noise
caused by high tension.
Otherwise, electrical shock may occur.
�
Place a dedicated ground more than 2 meters
away from other grounds and do not have it
shared with other electric appliances.
WARNING
12-401 CU-5E34NBE_OU EN_1.qxd 3/12/12 5:05 PM Page 16
Summary of Contents for CU-5E34NBE-C
Page 41: ......
Page 42: ...INSTALLATION INSTRUCTIONS CU 5E34NBE 852 6 4190 578 00 1 APPENDIX A A 1...
Page 84: ......
Page 104: ......
Page 124: ......
Page 144: ......
Page 164: ......
Page 166: ...2 1 5 m R410A...
Page 167: ...3 A A E A...
Page 173: ...9 2 3 5 5 15 x 40 15 5 5 3 OXI 5 20 10 50 25 15 15 4 40 5 2 2 20 5 5...
Page 175: ...11 3 3 1 3 5 26 3 2 2 7 3 3 3 4 1 30 50 2 8 9 3 4 10 11 RIDGID 11 10 8 7 0 0 5 1 2 R410A 9...
Page 179: ...15 1 B E 22 2 E 23 3 0 05 0 1 MPaG 0 5 1 2G B E 23 5 10 4 24 22 23 E B A B A E o 24...
Page 183: ...19 1 C 32 2 3 10 4 5 6 2 15 C OFF 7 HA 4P 9 8 O C 32...
Page 184: ......
Page 186: ...DC1203 0...