8.3.1. Soft Dry Operation Time Diagram
8.3. Soft Dry Operation
•
Soft Dry operation can be set using remote control.
•
Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room.
•
This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control.
•
When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF”
for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shown
in below figure.
•
However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit will
start to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.
22
CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
Summary of Contents for CS-W7DKE
Page 15: ...5 Refrigeration Cycle Diagram 15 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 16: ...6 Block Diagram 16 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 17: ...17 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 18: ...7 Wiring Diagram 18 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 19: ...19 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 75: ...14 3 2 CS W9DKE CU W9DKE 75 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 76: ...14 3 3 CS W12DKE CU W12DKE 76 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 87: ...87 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 89: ...19 2 Remote Control 89 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 91: ...TOP VIEW 91 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...