The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the
circuit of JX1 at indoor electronic controller.
8.5. Operation Control
(For 8.5.1 to 8.5.7 information applies only to Cooling and Soft Dry Operation)
8.5.1. Restart Control (Time Delay Safety Control)
•
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
−
Cooling operation - the compressor stops for 3 minutes (minimum) before resume operation.
−
Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
•
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
•
This phenomenon is to balance the pressure inside the refrigerant cycle.
8.5.2. 60 Seconds Forced Operation
•
Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake
air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at the
remote control is permitted.
•
The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle and
return back to the outdoor unit.
8.5.3. 7 Minutes Time Save Control
•
The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the
compressor ON temperature (A) and compressor OFF temperature (B) during the period.
•
This phenomenon is to reduce the built up humidity inside a room.
24
CS-W7DKE CU-W7DKE / CS-W9DKE CU-W9DKE / CS-W12DKE CU-W12DKE
Summary of Contents for CS-W7DKE
Page 15: ...5 Refrigeration Cycle Diagram 15 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 16: ...6 Block Diagram 16 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 17: ...17 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 18: ...7 Wiring Diagram 18 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 19: ...19 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 75: ...14 3 2 CS W9DKE CU W9DKE 75 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 76: ...14 3 3 CS W12DKE CU W12DKE 76 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 87: ...87 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 89: ...19 2 Remote Control 89 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...
Page 91: ...TOP VIEW 91 CS W7DKE CU W7DKE CS W9DKE CU W9DKE CS W12DKE CU W12DKE...