o
Timer
control
When ON timer activates when unit stops, previous operation resumes and restores last saved e-ion
operation status.
When ON timer activates during any operation, no change and carry on current operation.
When OFF timer activates during any operation, all operation stops and the latest e-ion operation status
is saved.
o
Indicator
When e-ion operation starts, e-ion indicator ON.
o
e-ion
Check
Mode
To check if e-ion is malfunctioning, press “e-ion” button and follow by “Check” button to enter e-ion check
mode and supplies power to the e-ion Air Purifying System.
If abnormal discharge is detected at filter (short-circuited) due to water or dust adhesion, etc., the e-ion
indicator blinks immediately.
o
Power
failure
During e-ion individual operation, if power failure occurs, after power resumes, e-ion individual operation
resumes immediately.
During combination operation, if power failure occurs, after power resumes, combination operation
resume immediately.
o
Error Detection Control
When e-ion indicator blink, it indicates error listed below:
e-ion Air Purifying system main connector to PCB is open:
Judgement Method
During e-ion operation (include during Patrol operation), e-ion Air Purifying system main connector to
PCB is opened.
Troubleshooting Methods
Connect the connector or stop operation (include during Patrol operation) to cancel the blinking.
Abnormal
Discharge
Judgement Method
During e-ion operation, when feedback voltage is -Lo (at microcontroller) is detected, it is judged
abnormal discharge and stops power supplies to the e-ion Air Purifying system.
The unit retries after 30 minutes and repeat for 24 times. (not applicable for e-ion Check Mode)
Troubleshooting Method
Press “e-ion” button or “OFF/ON” button to stop the operation and check the e-ion Air Purifying
system main connector to PCB.
After that, press “e-ion” button again to confirm the e-ion indicator not blinking.
The 24 times counter will be clear after 10 minutes of normal operation or when operation stops.
Error Reset Method
Press “OFF/ON” button to OFF the operation.
Press AUTO OFF/ON button at indoor unit to OFF the operation.
OFF Timer activates.
Press “e-ion” button during e-ion individual mode.
Power supply reset.
e-ion
breakdown
Judgement Method
When hi-feedback voltage (at microcontroller) supplied to filter during e-ion stop, due to PCB or
filter’s high voltage power supply damage.
Operations except e-ion continue. Both Timer indicator and e-ion indicator blink.
Troubleshooting Method
Press “e-ion” button or “OFF/ON” button to stop the operation.
Change main circuit board or filter’s high voltage power supply.
When lo-feedback voltage supplied to e-ion Air Purifying system during e-ion operation, e-ion
indicator and Timer indicator stop blinking.
Summary of Contents for CS-QE12MKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 24: ...24 10 2 Outdoor Unit ...
Page 52: ...52 15 3 Error Code Table ...
Page 53: ...53 ...
Page 80: ...80 16 1 3 To remove discharge grille ...
Page 81: ...81 16 1 3 1 To remove control board 16 1 4 To remove cross flow fan and indoor fan motor ...
Page 82: ...82 ...
Page 84: ...84 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU QE9MKE ...
Page 85: ...85 ...
Page 86: ...86 ...
Page 87: ...87 ...
Page 88: ...88 17 1 2 CU QE12MKE ...
Page 89: ...89 ...
Page 90: ...90 ...
Page 91: ...91 ...