Airflow direction (Horizontal, Vertical) Control
During any operation mode combines with Patrol operation, airflow direction follows respective operation
mode.
During Patrol individual operation if e-ion starts, only Auto Air Swing is allowed. Even if “Air Swing” button
is pressed, no signal is sent to air conditioner, and no change on LCD display.
During Patrol individual operation if e-ion stops, Airflow direction louver closed.
o
Indicator
When Patrol operation starts, Patrol Sensor indicator ON.
When e-ion operation starts based on dirtiness level, e-ion indicator ON.
o
Remote Control Receiving Sound
Normal
Operation
Î
Patrol Mode
: Beep
Patrol
Mode
Î
Stop
: Long Beep
Patrol
Mode
Î
Normal Operation
: Beep
Stop
Î
Patrol
: Beep
o
Timer
Control
When ON timer activates when unit stops, previous operation resumes and restored last saved patrol
operation status.
When ON timer activates during any operation, no change and carry on current operation.
When OFF timer activates during any operation, all operation stops and the latest patrol operation status
is saved.
o
Power
failure
During Patrol individual operation, if power failure occurs, after power resumes, Patrol individual
operation resumes immediately.
During combination operation, if power failure occurs, after power resumes combination operation
resume immediately.
o
Error Detection Control
The Patrol error detection control starts once the power is supplied to Patrol sensor. However, the error
will display when the Patrol operation is ON.
Error detection method:
If the Patrol sensor feedback is 0V or 5V continuous for 6 hours, Patrol sensor error occurs. However,
the error will display only when the Patrol operation is ON.
Patrol Sensor Control after error occurs
During any operation mode combines with Patrol operation
o
Power supply to Patrol sensor is OFF
o
Air conditioner normal mode operation continues with Patrol LED and Timer LED blinking and
“H58” is indicated.
o
Timer LED will always blinking and the Patrol LED continues blinking if the Patrol operation is
ON and stops blinking if the patrol operation is OFF.
During Patrol individual mode
o
Power supply to Patrol sensor is OFF
o
Patrol LED and Timer LED blinking and “H58” is indicated.
o
Timer LED will always blinking and the Patrol LED continues blinking if the Patrol operation is
ON and stops blinking if the Patrol operation is OFF.
Error cancel condition:
Power supply reset
Summary of Contents for CS-QE12MKE
Page 12: ...12 4 Location of Controls and Components 4 1 Indoor Unit 4 2 Outdoor Unit 4 3 Remote Control ...
Page 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Page 14: ...14 5 2 Outdoor Unit ...
Page 15: ...15 6 Refrigeration Cycle Diagram ...
Page 16: ...16 7 Block Diagram ...
Page 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Page 18: ...18 8 2 Outdoor Unit ...
Page 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 20: ...20 9 2 Outdoor Unit ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 24: ...24 10 2 Outdoor Unit ...
Page 52: ...52 15 3 Error Code Table ...
Page 53: ...53 ...
Page 80: ...80 16 1 3 To remove discharge grille ...
Page 81: ...81 16 1 3 1 To remove control board 16 1 4 To remove cross flow fan and indoor fan motor ...
Page 82: ...82 ...
Page 84: ...84 17 Technical Data 17 1 Operation Characteristics 17 1 1 CU QE9MKE ...
Page 85: ...85 ...
Page 86: ...86 ...
Page 87: ...87 ...
Page 88: ...88 17 1 2 CU QE12MKE ...
Page 89: ...89 ...
Page 90: ...90 ...
Page 91: ...91 ...