36
12.4. Thermostat Control
• Depending on differences between room temperature and setting temperature, compressor operation is decided and starts
operation.
• If temperature difference matches values shown below, thermostat switches off.
12.5. Indoor Fan Control
12.5.1.
Manual Fan Speed
• Fan operation can be set using remote control.
• The indoor fan is operated at High, Medium or Low speed according to remote control setting.
12.5.2.
Auto Fan Speed
• According to room temperature and setting temperature, indoor fan speed is determined automatically.
• The indoor fan will operate according to pattern below.
12.5.3.
Feedback Control
• Immediately after the fan motor is started, feedback control is performed once every second.
• During fan motor on, if fan motor feedback 2550 rpm or <50 rpm continuously for 10 seconds, the fan motor error counter
increased; fan motor is then stopped and restarted. If the fan motor error counter increased to 7, then fan motor error is detected.
Operation stopped and could not be restarted.
12.6. Outdoor Fan Operation
• Outdoor fan speed changes according to outdoor pipe temperature.
• The fan speed is controlled by the timing of turning the outdoor fan ON and OFF within an interval.
• There unit compares current temperature (T2) with previous (2 seconds before) temperature (T1) and decides the outdoor fan
ON time (X).
Outdoor fan ON time (X) is a variable with the range of 200ms to 1600ms or continuosly ON.
• Every 2 minutes, the outdoor pipe temperature is detected and the outdoor unit fan speed is changed automatically.
Cooling
0
C
Soft Dry
-1.0
C
Judgement
Outdoor fan ON time (X)
45
C T2
X = X + 100ms
40
C T2 45
C & T2 T1
X = X + 50ms
40
C T2 45
C & T2 T1
X = X
35
C T2 40
C
X = X
30
C T2 35
C & T2 T1
X = X - 50ms
30
C T2 35
C & T2 T1
X = X
T2
30
C
X = X - 50ms
Summary of Contents for CS-PC30JKF
Page 9: ...9 5 Dimensions 5 1 Indoor Unit Remote Control ...
Page 10: ...10 5 2 Outdoor Unit 5 2 1 CU PC30JKF ...
Page 11: ...11 5 2 2 CU PC36JKF ...
Page 12: ...12 6 Refrigeration Cycle Diagram 6 1 CS PC30JKF CU PC30JKF ...
Page 13: ...13 6 2 CS PC36JKF CU PC36JKF ...
Page 14: ...14 7 Block Diagram ...
Page 15: ...15 8 Wiring Connection Diagram 8 1 Indoor Unit 8 1 1 CS PC30JKF CS PC36JKF ...
Page 18: ...18 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Page 19: ...19 9 2 Outdoor Unit 9 2 1 CU PC30JKF ...
Page 20: ...20 9 2 2 CU PC36JKF ...
Page 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Page 22: ...22 10 1 2 Power Printed Circuit Board 10 1 3 Indicator Printed Circuit Board ...
Page 23: ...23 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU PC30JKF ...
Page 24: ...24 10 2 1 2 CU PC36JKF ...
Page 47: ...47 16 1 3 To remove discharge grille ...
Page 48: ...48 16 1 4 To remove control board 16 1 5 To remove cross flow fan and indoor fan motor ...
Page 49: ...49 ...
Page 50: ...50 17 Technical Data 17 1 Thermostat Characteristics Cooling Soft Dry ...
Page 51: ...51 17 2 Operation Characteristics 17 2 1 CS PC30JKF CU PC30JKF ...
Page 52: ...52 ...
Page 53: ...53 17 2 2 CS PC36JKF CU PC36JKF ...
Page 54: ...54 ...
Page 57: ...57 17 5 Sound Data 17 5 1 CS PC30JKF CU PC30JKF 17 5 2 CS PC36JKF CU PC36JKF ...
Page 62: ...62 18 2 Outdoor Unit 18 2 1 CU PC30JKF ...
Page 65: ...65 18 2 2 CU PC36JKF ...
Page 66: ...66 ...